T.7.1 Settings common to all Display models

When an error occurs, an error message appears on the bottom (or top) portion of the screen area.

Errors starting with RHxx / RJxx / RKxx / RMxx (Errors that occur when there are connection issues)

Errors starting with RAAA (Application errors)

Errors starting with RAAE (Run time errors)

REAA Errors

RFAA Errors

Errors starting with RHxx / RJxx / RKxx / RMxx (Errors that occur when there are connection issues)

The following error messages are displayed when there is a problem in the communication with the connected device (such as PLC).

*1 If the error occurred in all screens, please check the addresses set via functions which operate in all screens, such as System Data Area, Alarm, Global D-script, Global Window and Sampling (Historical Trend Graph). To check the addresses, from GP-Pro EX's [System Settings] window, select [Peripheral List] and see [List of Device/PLC Management Addresses].
5.4.14 System Settings [Peripheral List] Settings Guide
If the error occurred on specific screens, check the addresses for parts and functions that operate on those specific screens only.

Error Code

Error Message

Cause

Solution

RHAA006

(Driver Name): (Port Name) - Received data has parity error

An error occurred due to a lack of data received. The cause could be the noise or loose connection.

Please check the noise suppression and whether the connector is inserted properly.

If Memory-Link method is used, please check if the Data Length/Parity Bit of host side and the display side have the same settings.

For more detailed solutions, please refer to the following.

http://www.pro-face.com/trans/en/manual/1029.html

RHAA007

(Driver Name): (Port Name) - Received data has framing error

Please check the noise suppression and whether the connector is inserted properly.

If Memory-Link method is used, please check if the Data Length/Parity Bit of host side and the display side have the same settings.

RHAA008

(Driver Name): This model does not use Ethernet

An error occurred when a Ethernet driver is selected in GP-Pro EX as the [Device/PLC], but the project is transferred to a display model which cannot use Ethernet.

Please check if the display unit supports Ethernet. If it does, please check if the Display Type settings in the GP-Pro EX editor are correct.

RHAA009

(Driver Name): (Port Name) Cannot use the port

An error occurred when two or more driver types are selected to an identical COM port.

An error occurrs when the USB/SIO (RS-422/485) port flow control setting is not correct.

Please check the [Port] settings in GP-Pro EX's [Device/PLC].

When you are using the USB/RS-422/485 conversion adapter, set [Flow Control] to [None].

RHAA010

(Driver Name): TCP port number ***** is overlapped, or it is not completed to close the last TCP connection

TCP port number of the display unit side is overlapped, or the device/PLC is reset during communication.

(1) Check that the UDP port number in [Ethernet settings] does not overlap with the UDP port number in [Communication Settings]. If the UDP port number is overlapped, allocate a different port number.

(2) Reset the display unit.

RHAA011

(Driver Name): Connection was closed

An error occurred in the connection environment during communication.

Please check if the network environment is normal. Please specify the cause via procedures such as directly connecting PC, display unit and device/PLC, and then checking if IP address is recognized via PING command.

RHAA012

(Driver Name): UDP Port number is overlapped

An error occurred when UDP port number of touch panel side is overlapped.

Check that the UDP port number in [Ethernet settings] does not overlap with the UDP port number in [Communication Settings]. If the UDP port number is overlapped, allocate a different port number.

RHAA013

(Driver Name): COM1: The 9th pin has not been set to VCC (5V Power Supply). Please check your cable or connected equipment.

9th pin of COM1 is connected as RI input. (For example, set to use Isolation Unit (RS-232C Type))

Please designate [RI] in [RI/VCC] settings of GP-Pro EX's [Device/PLC].

RHAA033

(Node Name): Error has been responded for initial communication command (Error Code: (Decimal)[(Hex)])

Device/PLC is returning an error code on a communication request from the display unit.

Please check the device/PLC manual for details on error codes.

RHAA034

(Node Name): Error has been responded for device read command (Error Code: (Decimal)[(Hex)])

Device/PLC is returning an error code on a read request from the display unit.

Please check the device/PLC manual for details on error codes.

For more solutions with Omron Corporation PLCs, please refer to the following.

http://www.pro-face.com/trans/en/manual/1031.html

RHAA035

(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)])

Device/PLC is returning an error code on a write request from the display unit.

Please check the device/PLC manual for details on error codes.

RHAA036

(Node Name): Error has been responded for device read command (Error Code: (Decimal)[(Hex)] There are out of range devices)

Device/PLC cannot recognize the Read request of the address set via the display unit side, and return the error code. It might be set to request the address which is out of PLC address range on the display unit side.

(1) Please check the manual of device/PLC in use for the detail of receiving error codes.

(2) Please check if the address set is within the device/PLC device address range in use. *1

RHAA037

(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)] There are out of range devices)

The Device/PLC cannot recognize the Write request of the address set on the display unit side, and returns the error code. It might be set to request an address which is out of the PLC address range on the display unit side.

RHAA038

(Node Name): Error has been responded for device read command (Error Code: (Decimal)[(Hex)] There are write only devices)

Device/PLC cannot recognize the Read request of the address set via the display unit side, and return the error code. It might be set to request the write only address of device/PLC on the display unit side.

(1) Please check the manual of device/PLC in use for the detail of receiving error codes.

(2) Please check if the address is set to read the write only address. *1
When using parts such as Data Displays or Lamps that run read operations, please set to addresses that support read operations.

RHAA039

(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)] There are read only devices)

The Device/PLC cannot recognize the Write request of the address set on the display unit side, and returns the error code. It might be set to request the read only address of device/PLC on the display unit side.

(1) Please check the manual of device/PLC in use for the detail of receiving error codes.

(2) Please check if the address is set to write to the read-only address. *1
When using parts such as Switches, Data Displays (Allow Input), or Trigger Actions and D-scripts, that run write operations, please set to read/write addresses.

RHAA040

(Node Name): Illegal response for initial communication command

An error occurred on device/PLC side

Please check that the communication settings or the connected device settings are specified properly.

RHAA041

(Node Name): Illegal response for device read command

Please check that the communication settings or the connected device settings are specified properly.

For more detailed solutions, please refer to the following.

http://www.pro-face.com/trans/en/manual/1032.html

RHAA042

(Node Name): Illegal response for device write command

Please check that the communication settings or the connected device settings are specified properly.

RHAA043

Checksum error response for initial communication command

Please check that the communication settings or the connected device settings are specified properly.

RHAA044

(Node Name): Checksum error response for device read command

Please check that the communication settings or the connected device settings are specified properly.

RHAA045

(Node Name): Checksum error response for device write command

Please check that the communication settings or the connected device settings are specified properly.

RHAA049

(Node Name): Unknown devices exist in read devices

Wrong device and address are created via Indirect Address Designation.

Please check if settings of Indirect Address Designation are within the recognizable address range.

RHAA050

(Node Name): Unknown devices exist in write devices

RHAA051

(Node Name): Out of range devices exist in read devices (Address: (Device Address))

In the Data Display (Text Display) or D-script (memcpy or memset), area from the start address to the end address is not within the address range.

Please check if the settings which is across multiple addresses, such as Data Display (Text Display) or D-script, are within the address range. *1

RHAA052

(Node Name): Out of range devices exist in write devices (Address: (Device Address))

RHAA053

(Node Name): You cannot read the write only device (Address: (Device Address))

The Protocol driver detected read-out of the write only device, or write-in of the read only device

(1) Please check the manual of device/PLC in use for the detail of receiving error codes.

(2) Please check if the address is set to read the write only address. If Parts that perform reading operation such as Lamps and Data Display are used, please set the read address.

RHAA054

(Node Name): You cannot write the read only device (Address: (Device Address))

RHAA065

(Node Name): TCP connection open error (IP Address: (IP Address))

IP address and port number of device/PLC are not recognized.
The cause could be that the power of HUB or device/PLC is not ON, or cable is unplugged.

(1) Please check the settings of IP address and Port number on display unit side and device/PLC side.

(2) Please check if the network environment is normal.
Please specify the cause via procedures such as directly connecting PC, display unit and device/PLC, and then checking if IP address is recognized via PING command.

RHAA066

(Node Name): UDP target not found (IP Address: (IP Address))

RHAA067

(Node Name): Response timed out for initial communication command

The causes could be the following:

  1. The communication settings are not the same between display unit and PLC.

  2. Wiring has problems such as a wrong wire connection or loose connection.

  3. Selection of device/PLC is wrong.

  4. The power of device/PLC is not ON, or it is reset.

(1) Please check if the communication settings of display unit side and device/PLC side are the same. Please refer to "GP-Pro EX Device/PLC Connection Manual" for the details.

(2) Please reconfirm the wiring. Please check the cable and connector's insertion. About wire connection, please refer to "GP-Pro EX Device/PLC Connection Manual" for the details. When using COM 2, please check if Online Adaptor (CA4-ADPONL-01) is connected.

(3) Please reconfirm the GP-Pro EX [Device/PLC Settings].

For more solutions with Mitsubishi Electric Corporation PLCs, please refer to the following.

http://www.pro-face.com/trans/en/manual/1033.html

RHAA068

(Node Name): Response timed out for device read command

RHAA069

(Node Name): Response timed out for device write command

RHAA070

(Node Name): The cable has been disconnected or the target has been powered off

The command cannot be sent due to the cause that the device/PLC power is not ON or cable is unplugged, etc.

(1) Transferring to GP3**1 series using GP3**0 series. Check if the Display Type settings match the display model in use.

(2) Please check if the device/PLC power is ON.

(3) Please check if the cable wiring is correct, and if cable is connected properly.

RHAA071

(Node Name): The extend unit (Unit Name) is not implemented

The Expansion Unit is not recognized.

Please check if the Expansion Unit is correctly attached.

RHAA072

(Node Name): Illegal read request because this device has been off scan

A read request was made through sampling, extended D-script, Pro-Server EX, to the device in off-scan mode.

A read request was made through sampling, extended D-script, Pro-Server EX, to the device for which communication scan has been stopped. Turn OFF the appropriate bit*2 between LS9550 and LS9559 and start the communication scan of the connected device.

7.3 Disconnecting Multiple Connected Devices/PLCs

RHAA073

(Node Name): Illegal write request because this device has been off scan

A write request was made through a script, a touch, Pro-Server EX, to the device in off-scan mode.

A write request was made through a switch, D-script, extended D-script, Pro-Server EX, to the device for which communication scan has been stopped. Turn OFF the appropriate bit*2 between LS9550 and LS9559 and start the communication scan of the connected device.

7.3 Disconnecting Multiple Connected Devices/PLCs

RHAA084

(Node Name): Too many requests to write. The request was ignored.

A write operation was continued at timing which exceeds the processing speed of the communication driver.

Example) For a connected device set up with a baud rate of 9600, if you continue to write with the same timing as tag scan counter updates.

Check if a D-script or other setting has been specified which continues writing at fast speed.

This error may occur when you use D-script with a bit that changes ON/OFF at a high rate (such as the LS9400 tag scan counter) to continually write to a device that communicates at a low speed (such as 9600 bps).

RHAA085

(Node Name): Too many requests to read. The request was ignored.

A read operation was continued at timing which exceeds the processing speed of the communication driver.

Example) When reading continuously, with the same timing as tag scan counter updates, from a connected device that has a baud rate of 9600.

Check if a D-script or other setting has been specified which continues reading at fast speed.

This error may occur when you use D-script with a bit that changes ON/OFF at a high rate (such as the LS9400 tag scan counter) to continually read from a device that communicates at a low speed (such as 9600 bps).

RHAA088

COM1: The station number of Multilink function duplicates that of another device

The station number of Multilink function duplicates that of another device.

Verify the station number and re-set it so it does not duplicate.

RHAA089

COM1: The address of the Multilink communication information is different from the other station

The address of the Multilink communication information is different from the other station

Set the Multilink communication information address to the same address on the Multilink Network.

RHAA090

Response timed out from external device

Multilink communication surveillance timeout lapsed (60 seconds).

Verify network.

RHAA091

COM1: Checksum error response for Multilink command

Checksum error occurs.

Verify communication settings.

RHAA092

COM1: Failed to update the Multilink communication information

Failed to update the Multilink communication information

Verify Multilink communication information and communication settings

RHAA093

COM1: Since cannot join to Multilink token, the request was unreceivable

Write request and read requests occurred (except for read requests that run all the time). Communication has failed for 2 hours.

Add the display unit to the list of Multilink stations. Check if any display units are monopolizing the PLC for more than 2 hours.

RHAA113

Communication system assertion (****)

The device set up in the project is incorrect. Inside the brackets is the error content.

Check the device set up in the project.

*2 The setting range of the bit addresses for controlling running and stopping communication scans are internal device addresses LS9550 to LS9557. Each device/ PLC address starting from Bit 0 is assigned sequentially to each driver's device/PLC starting from the first unit.

Example, you can set the bit addresses of LS9550 to control communication scans for units 1 to 16 in Driver1.
LS9550

Bit 0: Scans ON/OFF Driver1's first PLC.
Stops the scan (scans OFF) of Driver1's first PLC by turning ON Bit 0. Turn OFF bit 0 to resume the scan.
You cannot stop the communication scan of a device specified with the System Area Start Address. However, if you are not using the System Data Area, you can stop the communication scan.
5.4.6 System Settings [Display Unit] - [System Area] Settings Guide
You can set the LS area with 32 bit addresses on some devices/PLCs. In this case, the bottom 16 bits are used for bit addresses controlling the communication scan.
When you turn OFF the communication scan, the displayed part's data will remain. However, if you change screens and then display the screen again, the part's data will not be displayed.

Errors starting with RAAA (Application errors)

Error Code

Error Message

Cause and Troubleshooting

Browse

RAAA001

No project data exists. (Transfer a project.)

No project file exists.

Transfer a project.

34.2.1 USB Transfer - Transferring from Computer to Display Unit (Send)

34.3.1 Transfer - Transferring from Computer to Display Unit (Send)

RAAA002

The project data size exceeds the capacity.

The project data size exceeds the maximum capacity*. Or, the number of screens exceeds 16,000 files. Reference the GP-Pro EX Project Information, and make sure it does not exceed the general capacity.

* The maximum capacity of the project data size varies depending on the Display model. (Example: 8 MB for GP-3500T).

3.6 Viewing Project Information

RAAA003

The project data is invalid. (Transfer the project again.)

There is an error in the project file.

Transfer the project again.

34.2.1 USB Transfer - Transferring from Computer to Display Unit (Send)

34.3.1 Transfer - Transferring from Computer to Display Unit (Send)

RAAA004

The system screen is invalid. (Execute forced transfer.)

The system screen does not exist or is invalid.

Force a transfer.

34.12.1 Transfer Settings Guide

RAAA005

The specified initial screen number does not exist.

The screen cannot display because the screen number designated in the Initial Screen Settings does not exist in the project. Change the initial screen number or add the screen. The screen number designated in the parentheses is displayed.
Also displays when you first attach the RTC Battery Set (option) to the GP-4100 Series (Color Model).

5.4.2.2 Display Unit [Display] - Display Settings

RAAA006

Project contains unsupported functions and cannot be displayed.

The current model includes functions which the runtime program cannot recognize. Please remove the unsupported function and transfer again.

The editor and runtime versions may not match. Update the runtime version.

-

RAAA007

The no. of parts in the screen exceeds the limit. (MAX 384)

The number of parts that can be operated on a single screen has reached the upper limit.

The number of parts exceeds the limit during a screen change or when opening a window. Make sure to set parts within the permitted range.

2.2 Number of Parts/Features That Can Be Set

RAAA008

The font ( **** ) does not exist. (Transfer the font with the project.)

The font you are trying to display does not exist in the system. Download the font into the system.

The following table shows the font names.

Japanese Standard

English Standard

Korean Standard

Chinese (Simplified Character) Standard

Chinese (Traditional Character) Standard

Russian (Cyrillic) Standard

Japanese Stroke

English Stroke

Korean Stroke

Chinese (Simplified Character) Stroke

Chinese (Traditional Character) Stroke

Russian (Cyrillic) Stroke

Thai Stroke

6.5 Font Settings Guide

RAAA010

A CF/SD card is not inserted, or the CF card hatch is open.

A CF Card/SD Card is not inserted, or the CF Card cover is open, so unable to access the CF Card/SD Card. Insert a CF Card/SD Card. Or close the CF card cover.

GP3000 Series Hardware Manual

RAAA011

Failed to start from the CF/SD Card.

  • Despite DIP SW1 being turned ON, the necessary files to start from the CF Card/SD Card do not exist. Or the necessary file may have an error. Copy the startup project to the CF/SD Card again.
    Or, if the settings to access the CF/SD Card are not created intentionally, verify the following. Previous settings may still remain.

  1. Select [Display Unit] - [Operation Settings] - [Memory Card Settings] and check the [Screen Capture] settings.

  2. Select [Common Settings] - [Sampling] and check [Display/Save in CSV] for each registered sampling.

  3. CF/SD file write function of the D-Script

  4. Select [Common Settings] - [Operation Log Settings] and check the settings.

When using one of the following models, the SD Card startup program may be damaged.

  • SP5000 Series (excluding Open Box)

  • GP4000 series (excluding the GP-4100 series)

Copy the startup project to the SD Card again.

  • When the system on the display unit is newer than the system that you are transferring, you may not be able to transfer. Use the Memory Loader with the latest GP-Pro EX system to transfer.

34.8 Transfer using external storage

RAAA012

The project data contains functions that are not supported by this model.

When running on display unit:

The current model includes functions which the runtime program cannot recognize. Change to a model that supports the feature or remove it.

Please refer to the following for supported features.

1.5 Supported Features

When running simulation:

Simulation does not support all features. You can only simulate supported features.

Please refer to the following for unsupported features.

33.7.1 Restrictions on Simulation

-

RAAA013

USB storage location not found.

The USB storage device cannot be accessed due to the poor connection or recognition problem. Check if the USB storage device is connected. If connected, disconnect and then reconnect the USB storage device.

RAAA014

Failed to start from USB storage.

  • The file required for startup from the USB storage device does not exist. Or the necessary file may have an error.
    Check that the startup file "boot.cfg" and the "pj001" folder are located in the root of USB storage.
    When using one of the following models, the USB storage startup program may be damaged.

  • SP5000 Series Power Box

  • GP4000 series (excluding GP-410*)

  • LT4000 Series

  • ST6000 Series

  • STM6000 Series

  • STC6000 Series

  • ET6000 Series

Copy the startup project to the USB storage again.

  • When the system on the display unit is newer than the system that you are transferring, you may not be able to transfer. Use the Memory Loader with the latest GP-Pro EX system to transfer.

34.8 Transfer using external storage

RAAA015

Unable to go off-line.

Offline mode files do not exist, or are damaged. Please run a forced transfer.

-

RAAA016

Bitmap font unavailable. (Please transfer a project with this font.)

You are using a font that is not registered in the [Image Font] settings. Add fonts used in the project, and transfer again.

RAAA017

Not supporting the format of the CF/SD Card being used.

External storage has been formatted in a format not supported. If external storage with capacity over 2GB has been formatted as FAT16, reformat as FAT32.

RAAA018

Unable to use USB storage. Its capacity level is unsupported.

RAAA019

Because the image font is set, it is not possible to display it.

When the System Settings [Synchronize with Text Table] are turned ON, the Data Display (Text Display) cannot use image fonts. Please change to Standard Font or Stroke Font.

RAAA022

Cannot remove the "SD Card".

Unable to remove the SD Card because the SD Card is being accessed. Stop the function that is accessing the SD Card.

5.3 Remove an External Storage Device

RAAA023

Cannot remove the "USB storage".

Unable to remove the USB storage because the USB storage is being accessed. Stop the function that is accessing the USB storage.

5.3 Remove an External Storage Device

RAAA024

(***) (+++) failed (xxx)

External storage access error occurred. Check the status of external storage, and run the operation again.

If the same error occurs, please contact customer support.

(*** is the external storage in use, +++ is the operation, xxx is the function name.)

  • To hide this error message, regardless of the model you are using clear the [Do not display when storage access failed] check box.
    5.4.4.4 Display Unit [Mode] - Memory Card Settings

  • This error message is also displayed if external storage is not installed.

5.3 Remove an External Storage Device

RAAA025

Root certificate has expired.

The specified root certificate has expired. Update the SSL certificate (*.perm) and transfer the project file again.

If the root certificate has not passed the certification period, It may be because of the display unit's clock being out of sync (passed the certification period). Please specify proper clock data.

5.4.21 System Settings [E-mail] Settings Guide

RAAA050

Clock Setting Error

When changing the clock data, the data write to the clock IC failed.

Set up value is invalid as clock data. Please specify proper clock data.

If you are using LT4000 series, the project file may have been transfered from GP-Pro EX Ver.3.12. Transfer a project file from Ver.3.5 or later.

The IC chip may be broken. Please contact customer support.

5.2 Adjusting the Time

1.5.18.1 For Those Using the LT4000 Series

RAAA051

Low battery

Rechargeable battery has run out. Supply power to the display unit and fully recharge the battery. Battery will be charged up to the level at which it can run backup 24 hours after the power is turned ON. It takes up to 120 hours (5 days) to complete charging. Check the Hardware Manual for charging times required by the display unit.

Hardware Manual of the display unit you are using

RAAA052

There is a problem with the hardware.

(****) indicates where the problem is in the Display.

For example, when an error occurred with the LAN port, "LAN" is displayed. This may be caused by a fault in the display unit. Please contact customer support.

-

RAAA053

Running out of power in the backup battery. Please change the battery.

-

Hardware Manual of the display unit you are using

RAAA054

The backup data has been deleted.

Data in the backup memory (SRAM) has been deleted due to the backup battery running out.

-

RAAA055

Clock has been initialized.

The clock data has been initialized due to the clock data running out.

5.2.2 Procedure - Adjusting the Clock (When Using the System Data Area)

RAAA060

Failed to save backup data

Failed to save backup data to internal memory. Please run back up again. If this occurs frequently, the maximum possible number of saves to internal memory may have been exceeded, or the unit is damaged. Please contact customer support.

-

RAAA061

Failed to read backup data

There is a problem with the backup data saved to internal memory. Previously, while saving the backup the power may have been disconnected. Please run back up again. If this occurs even though the backup is run again, the maximum possible number of saves to internal memory may have been exceeded, or the unit is damaged. Please contact customer support.

RAAA062

Unable to use backup data

Unable to save or read backup data in internal memory. The maximum possible number of saves to internal memory may have been exceeded, or the unit is damaged. Please contact customer support.

RAAA063

Failed to get clock data

Device/PLC is not supporting updating the clock. Please check if the device/PLC supports clock updates.

5.5.2 Common - Clock Update Settings

RAAA064

Failed to save the IP address. Restart the display unit.

Failed to save the IP address obtained from the DHCP server. Restart the display unit.

-

RAAA065

Failed to connect to the DHCP server.

The cables may not be correctly connected. Check the cable connection status.

-

RAAA066

An error occurred while communicating with the DHCP server.

An error may have occurred while communicating with the DHCP server. Verify the DHCP server settings and network environment.

-

RAAA067

The display unit was restarted as the DHCP server updated the IP address.

The IP address has been forcibly changed by the DHCP server.

-

RAAA100

The system start device address is incorrect.

The system device start address is not set correctly or has an error.

Set the correct address while in offline mode, or transfer a project.

5.4.6 System Settings [Display Unit] - [System Area] Settings Guide

RAAA101

Illegal/Undefined Device Address

Appears when the device address used by a part or function is invalid.

Edit the device address, and transfer again to recover.

-

RAAA102

Failed to read from the Device/PLC.

Failed to read from the device/PLC.

Confirm the connection status, such as whether the communication cable is disconnected, etc.

The part name is entered in the parentheses.

-

RAAA103

The specified address is incorrect.

The designated address is incorrect. Make sure to set the correct address. The part name is entered in the parentheses.

-

RAAA110

Remote PC Access error. Unable to recover.

An internal initialization error or system error occurred.

Restart the display unit, or review the screen settings.

M.15.1 System Menu - Offline, CF/USB (or SD/USB), Error, Reset

RAAA111

Unable to certify Remote PC Access server.

The password is invalid.

Check if the password matches the password specified on the Server PC.

36.3 Display or Operate a Computer from the Display Unit

RAAA112

Failed to connect to Remote PC Access server.

No Server PC is found. Or failed to connect to the server.

Check if the IP address matches with that for the Server PC.

Check if the Server PC is active.

Check the settings on the Server PC.

Check if the Server PC Firewall is enabled.

RAAA113

Connecting to Remote PC Access server.

The previous disconnection process is not completed.

Wait for a while (75 seconds maximum), and then retry connecting to the server.

-

RAAA114

Missing Remote PC Access license key code. Enter key code in offline mode.

With GP-Pro EX, the RPA function key code has not been set up. Enter an RPA key code in offline mode.

M.5.3 Setting up GP-Viewer EX or Remote PC Access License

RAAA115

PC input is restricted.

[Touch Input Inhibition] is set in the RPA window display. Disable the setting of [Touch Input Inhibition].

36.4.1 Remote PC Access Window Display Setting Guide

RAAA120

D-Script Error (The specified function does not exist or the function has an error.)

The function called in the D-Script does not exist. Or there is an error in the function. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA121

D-Script Error (These functions are nested to 10 levels or more.)

Functions in the D-Script are nested to 10 levels or more.

Reduce the levels in the "if" and "loop" structures.

* A nesting level is when function A calls function B, and then again when function B calls function C (function calling level).

22.11.11.3 loop - endloop

RAAA122

D-Script Error (An expression exists, that is not supported by this version.)

An incompatible function was found in the project's D-Script. Update the runtime version.

-

RAAA123

D-Script Error (The SIO operation function is used in a condition where no Device/PLC has been set.)

SIO Operation functions are used in a D-Script while the device/PLC settings are not set. Configure the device/PLC settings.

5.4.18 System Settings [Script I/O] Settings Guide

RAAA124

The D-Script has an error.

There is an error in the used D-Script. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA130

Global D-Script Error. (The Total Number of Global D-Scripts exceeds the maximum of 32.)

The total number of Global D-Scripts exceeds the limit. The maximum number of Global D-Scripts available is 32 (each function also counts as one script).

22.10.1 D-Script/Global D-Script Restrictions

RAAA131

Global D-Script Error.
(The total number of devices exceeds the maximum of 255.)

The total of all devices in the Global D-Script exceeds the limit of 255 devices. Reduce the number of used devices by using the Memory Operation function, etc.

RAAA132

Global D-Script Error (The specified function does not exist or the function has an error.)

The function called in the Global D-Script does not exist. Or there is an error in the function. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA133

Global D-Script Error (These functions are nested to 10 levels or more.)

Functions in the Global D-Script are nested to 10 levels or more.

Reduce the levels in the "if" and "loop" structures.

* A nesting level is when function A calls function B, and then again when function B calls function C (function calling level).

22.11.11.3 loop - endloop

RAAA134

Global D-Script Error (An expression exists, that is not supported by this version.)

An incompatible function was found in the project's Global D-Script. Update the runtime version.

-

RAAA135

Global D-Script Error (The SIO operation function is used in a condition where no Device/PLC has been set.)

SIO Operation functions are used in a Global D-Script while the device/PLC settings are not set. Configure the device/PLC settings.

5.4.18 System Settings [Script I/O] Settings Guide

RAAA136

The Global D-script has an error.

There is an error in the used Global D-Script. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA140

Extended D-Script Error (The total no. of functions exceeds the maximum of 255.)

The total number of Extended Scripts exceeds the limit. The maximum number of Extended Scripts is 255.

Reduce the number of scripts by combining two scripts into one, etc.

22.10.2 Extended Script Restrictions

RAAA141

Extended D-Script Error (The specified function does not exist or the function has an error.)

A function called in the Extended Script does not exist. Or there is an error in the function. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA142

Extended D-Script Error (These functions are nested to 10 levels or more.)

Functions in the Extended Script are nested to 10 levels or more.

Reduce the levels in the "if" and "loop" structures.

* A nesting level is when function A calls function B, and then again when function B calls function C (function calling level).

22.11.11.3 loop - endloop

RAAA143

Extended D-Script Error (An expression exists, that is not supported by this version.)

An incompatible function was found in the project's Extended Script. Update the runtime version.

-

RAAA144

Extended D-Script Error (The SIO operation function is used in a condition where no Device/PLC has been set.)

SIO Operation functions are used in a Extended Script while the device/PLC settings are not set. Configure the device/PLC settings.

5.4.18 System Settings [Script I/O] Settings Guide

RAAA145

The Extended D-Script has an error.

There is an error in the used Extended Script. Check the command format.

22.11 Built-In Function (Instruction) / Conditional Expressions

RAAA150

Incorrect password.

The security feature's password input is incorrect. Confirm that the input is correct (upper-case/lower-case letters, and so on) and enter the password again.

23.11 Password/User ID Input Window

RAAA151

Change the screen from the host.

This appears when a screen change occurs from the PLC (host) by the forced screen change method, and you cancel the displayed password input.

If you want to cancel, make sure to use a cancel notification bit and return to the previous screen from the PLC (host).

-

RAAA152

Cannot use the COM port.

This appears when the COM port you are trying to use is already in use by another feature. Check the settings again.

7.4 Changing a Device/PLC

RAAA153

No dictionary file was found.

The Japanese FEP dictionary file does not exist in internal memory or in the CF Card/SD Card. Transfer the project data again.

-

RAAA154

The specified filing data cannot be used with this project.

This appears if the designated filing data does not match the project data when transferring filing data from external storage to backup memory (SRAM). Make sure to use filing data that matches the project data.

26.11 Filing Data Flow

RAAA155

The IP address duplicates that of another device. Please change the address of either this machine or the other. (IP:***.***.***.***,
MAC:**:**:**:**:**:**) *1

A machine with the same IP address exists on the network. Change the IP address of this machine or of the other machine.

34.2.1 USB Transfer - Transferring from Computer to Display Unit (Send)

RAAA156

The COM port 9-pin could not be set to VCC (5V power supply). Please check your cable or connected equipment.

The COM port 9-pin could not be set to VCC (5V power supply). Check the COM port connection cable and the machine it is connected to. Then reset the machine or verify the project's script settings are set to a 5V power supply.

5.4.18 System Settings [Script I/O] Settings Guide

RAAA157

Cannot put the Device/PLC into offscan state when the system start device address is assigned to it.

The connected device (main PLC) assigned to the system start device address has been set to off-scan mode. You cannot normally set the main PLC to off-scan mode. However, it can be set by changing the setting to not use the system data area. Otherwise, cancel the off-scan setting.

5.4.6 System Settings [Display Unit] - [System Area] Settings Guide

RAAA158

Communication problem with the conversion adapter.

No conversion adapter is connected although the system is set to Enable. Connect the conversion adapter.

5.4.3 System Settings [Display Unit] - [Operation] Settings Guide

RAAA160

Function Expansion Memory is not installed (extended alarms).

The project file is configured to use function expansion memory, but the display device does not have function expansion memory installed. There are two solutions below. Select the appropriate method.

  1. First, turn off display device power. Next, install function expansion memory on the display and then turn the display power on again.

  2. First, use GP-Pro EX to open the project file. Next, change the settings so function expansion memory is not used and then send them to the display.

-

RAAA161

Function Expansion Memory is not installed (extended text table).

The project file is configured to use function expansion memory, but the display device does not have function expansion memory installed. There are two solutions below. Select the appropriate method.

  1. First, turn off display device power. Next, install function expansion memory on the display and then turn the display power on again.

  2. First, use GP-Pro EX to open the project file. Next, change the settings so function expansion memory is not used and then send them to the display.

-

RAAA162

It cannot be used due to abnormalities in the Enhanced Recipe Data (%s).

An abnormality has occurred in the Enhanced Recipe Data for some reason. Alternatively, the system on the display unit may be old.

Transfer the enhanced recipe data. Alternatively, use the Transfer Tool to execute a forced transfer.

RAAA163

Save processing for the Enhanced Recipe Data (GroupID=%05d) did not complete.

Element values edited with the Enhanced Recipe Data List are displayed when a project is terminated or when the display unit's power runs out while saving. Verify whether the edited element values are normal.

-

RAAA170

The password is invalid.

The security feature's password input is incorrect. Confirm that the input is correct (upper-case/lower-case letters, and so on) and enter the password again.

23.5.3 Log in/Log off

RAAA171

The password is a duplicate.

The password has already been registered. Please set up a different password.

23.8.2 Operation - Changing the Password from the Password Change Screen

RAAA172

User ID has not been registered

Attempted to login with an unregistered User ID. Input the registered User ID.

RAAA174

New password does not match

Password entered in [Confirm Password] does not match [New Password]. Input the correct password.

RAAA175

It is necessary to log in.

You must login to update the security information.

23.5.3 Log in/Log off

RAAA176

Duplicate User ID given.

The same User ID has already been registered. Please set up a different User ID.

23.8.2 Operation - Changing the Password from the Password Change Screen

RAAA177

Reached the maximum number.

Exceeded the maximum number (100) of User ID's. Please remove unnecessary User ID's.

RAAA180

The time was adjusted to daylight saving time.

If [Time Adjustment (Daylight Saving Time)] is enabled in the [Display Unit]'s [Time Zone Settings] settings, the time on the display unit was adjusted in accordance with the start/end of daylight saving time.

To avoid automatic adjustment of time, disable the daylight savings time settings.

M.17.2.10 Main Unit - Time Zone Settings

RAAA181

The connection was interrupted. Connection password is not supported by the unit.

Transfer using the Transfer Tool included in GP-Pro EX Ver4.09.150 or later.

RAAA182

The connection was interrupted. Set the connection password in offline mode.

The password settings are inconsistent. Please edit the connection password in offline mode.

M.17.4.3 Security Settings - Connection Password

RAAA192

Cannot use the RemoteHMI port (****).

From the [System Settings] window's [Display Unit] link, in the [Remote Viewer] tab, the port number specified for [Pro-face Remote HMI] is conflicting with other applications such as the Pro-face Remote HMI Server. Please change the port number.

The port number is entered in parentheses.

M.17.2.9 Main Unit - Remote Viewer Settings

RAAA193

Only one Historical Trend Graph with the Historical Data Display feature enabled can be placed on a screen.

On a single screen you can draw only one Historical Trend Graph part with the Display Historical Data function enabled.

19.13.1.9 Historical Trend Graph - Display Historical Data

RAAA200

Error occurred at system startup. Use the Transfer Tool to run a forced transfer operation.

Error found in the necessary files for startup.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA201

Error found in the font data.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA202

Error found in the LAN configuration file.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA203

There are issues in part of the project file.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA204

Did not succeed to start the Runtime System.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA205

Error occurred at system startup.

Use the Transfer Tool to run a forced transfer operation.

-

RAAA206

Error occurred during initialization of the internal memory.

Use the Transfer Tool to run a forced transfer operation.

-

*1IP addresses are shown as decimal, MAC addresses are shown as hexadecimal.

Errors starting with RAAE (Run time errors)

Error Code

Error Message

Cause and Troubleshooting

Browse

RAAE001

Unable to restore history data.

If the history data file is damaged, the checksum of the history data file does not match, and the previous history data is abnormal, this error message appears. In this case, restart the display unit after clearing the history data.

-

RAAE002

History data too big. Unable to restore history data.

If the volume of the stored history data file is larger than the size specified in the GP-Pro EX, and the previous history data is abnormal, this error message appears. Normally, this error does not occur but may occur when a history data file is exchanged. In this case, restart the display unit after clearing the history data.

-

RAAE003

There is no history to restore. Unable to restore history data.

If no history data file exists and the previous history data file is also not normal, this error message appears. When the system fails while saving a history data file or a history data file is deleted, this error occurs. In this case, restart the display unit after clearing the history data.

-

RAAE004

Recent history data is corrupted. Restoring previous history data.

If no history data file exists and the previous history data file is normal, this error message appears. When the system fails while saving a history data file or a history data file is deleted, this error occurs. In this case, restore the previously saved history data and then restart the display unit.

-

RAAE005

Recent history data is too big. Restoring previous history data.

If the volume of the stored history data file is larger than the size specified in GP-Pro EX, and the previous history data is normal, this error message appears. Normally, this error does not occur but may occur when a history data file is exchanged. In this case, restore the previously saved history data and then restart the display unit.

-

RAAE006

Recent history data does not exist. Restoring previous history data.

If the system failed while saving a history data file, this error message appears. When the history data file has already been opened by other software, or the history data file storage folder does not exist, this error occurs. In this case, the current history data cannot be saved.

-

RAAE007

Failed to save the backup file.

This message appears when the system cannot open or fails to save the history data file. In this case, the current history data cannot be saved.

-

RAAE008

The write filter is enabled. A file cannot be output to a drive that has this setting enabled.

On Windows Embedded machines, drives installed with an OS have a write filter (write protection) set to the drive. In this case, the current history data cannot be saved. Change the write to destination for the file or disable the write filter.

-

RAAE009

[LanSys.cfg] File is missing. Using initial value.

If no Lansys.cfg file exists, this error message appears. In this case, the local node name and port settings will be reset to the initial settings. Re-enter the local node name and port while in offline mode.

-

RAAE010

[system.cfg] File is missing. Using initial value.

If no system.cfg file exists, this error message appears. In this case, all settings in [Display Unit] will be reset to the initial settings. Transfer the project file again.

-

RAAE011

[CF/SD Card] path is too long (MAX:200)

The CF Card/SD Card reference destination path specified in the [Project (F)] menu [Property (I)] - [Destination Folder (C)] is too long.
Set up 200 characters or less in the destination folder path, and transfer the project again.

38.10.1.4 WinGP Settings - Set Destination Folder

RAAE012

[USB Storage] path is too long. (MAX:200)

The USB storage destination path is too long. From the [Project (F)] menu, point to [Information (I)], and click [Destination (C)].
Set up 200 characters or less in the destination folder path, and transfer the project again.

38.10.1.4 WinGP Settings - Set Destination Folder

RAAE013

Failed to start the Memory Loader.

There is no boot data in the root folder (directory) of the external storage. Alternatively, a file error may have occurred. Try running [Create Backup File] once more using the Transfer Tool.

34.12.2 Memory Loader

REAA Errors

Error Code

Error Message

Cause and Troubleshooting

Browse

REAA010

Transfer NPX changes: Unable to run Action/Data Transfer (***). Reason: ***

NPX information does not match between the transmission source and destination nodes for the "Action/Data Transfer". Please transfer the network project to all associated nodes for the "Action/Data Transfer".

-

REAA011

Individual transfer setups do not match. As a result, unable to run Action/Data Transfer.

[Compare NPX project on connection] setting does not match between the transmission source and destination nodes for the "Action/Data Transfer". In order to use the [Compare NPX project on connection] setting's [Changes] option, all associated nodes must be use the same setting. Please transfer the network project to all associated nodes.

-

REAA012

Data transfer information in the source and destination nodes do not match.

NPX information does not match between the transmission source and destination nodes for the "Action/Data Transfer". Please transfer the network project to all associated nodes for the "Action/Data Transfer".

-

REAA013

Data transfer information in the source and destination nodes do not match.  (Location does not match ***)

NPX information does not match between the transmission source and destination nodes for the "Action/Data Transfer". Please transfer the network project to all associated nodes for the "Action/Data Transfer".

-

REAA014

Data transfer destination node and runtime versions are not compatible.

Runtime version does not match between the transmission source and destination nodes for the "Action/Data Transfer". Please update the runtime version in all associated nodes for the "Action/Data Transfer".

-

REAA016

Could not use the *** port (number: ***)

Opening the *** (UDP or TCP) port number (***) failed. The system port number may have already been used. Please check the system port number and use available one.

-

REAA017

Attempted to access a write-protect area (***)

You cannot write to the write-protected area (LS0000 to LS0019, LS2032 to LS2095, LS9000 to LS9999) using a D-script or across the network. Please do not write data to the write-protected area using a D-script or across the network.

-

REAA018

Attempted to access a device outside the address range (***)

A device beyond the valid device range was accessed. Be sure to use the address in the device range.

Enter the correct Transfer operation password.

REAA021
REAA022

An invalid ID has (Node, Device, Address) has been specified.

An invalid ID was specified. Attempted to access a nonexistent device. Force the transfer of the files.

M.12.3 Forcing the transfer of project files

REAA026
REAA027
REAA028

Illegal/Undefined Device Address

An invalid device was specified. Attempted to access a nonexistent device. Force the transfer of the files.

REAA029

Unable to use device's Device ID ([indirect device])

You are specifying a device ID that is not registered in the project or a device ID that is not the same series as the [Indirect Device]. Please specify a device ID that matches the [Indirect Device] series.

When an indirect device address is specified to the following parts, after the device ID that does not exist is specified, when it is switched to a device ID that exists, an error message is displayed. An error message is displayed; however, subsequently, it operates properly.

  • [Word Address] in the Text Alarm Parts [Sub-Display]

  • [Remote PC Access Bit Address] in the RPA Window Display Unit

  • Movie Player [Status Word Address 1], [Status Word Address 2]

7.9.1 System Settings [Device/PLC] Settings Guide

REAA064

A communication error occurred during communication with the destination node. Please confirm that the network connection to the node has been properly established.

A: Server is down. (Server is not running.)

B: Network failure.

C: Server is busy. GP-Viewer EX on another machine is retrieving screen and storage data.

D: Server is busy. GP-Viewer EX on another machine is updating screen data on the server.

Check that the network and cables between this display unit and the target unit are properly established and connected. When this display unit is an Ethernet Multilink slave, confirm that the master display unit is a compatible model.

REAA065
REAA066

The destination node did not respond within the specified time. Please confirm that the network connection to the node has been properly established.

Check that the network and cables between this display unit and the target unit are properly established and connected.

REAA071

Connection failed. Runtime versions do not match.

Operation cannot be started because the runtime versions between the master and slave units are different.

Forcibly transfer the system using GP-Pro EX.

REAA072

Unable to run process. Ethernet Multi-link integrity check is incomplete.

The connection availability check from the slave unit to the master unit may not be completed because the master and slave unit connection may not have established or has just been established.

The connection availability check from the slave unit to the master unit may not be completed because the master and slave unit connection may not have established or has just been established.

Check the connection between the master and slave units. Or, try the process again.

REAA089

In the Ethernet Multilink Settings, this display unit's IP address or invalid one is set up as the Master IP Address.

Please check the settings and transfer the project data again, or change this display unit's IP address.

The slave display unit's master IP address is the IP address of this node, or the IP address is invalid.

Consequently, communication cannot be started and runtime cannot be initiated

Change the master GP's IP address in the message and transfer the screen project again.

Or, change the IP address of this display unit.

REAA090

Access to the master node denied.

The IP address filtering function is enabled but the IP address of the display unit has not been registered.

Register the IP address of the display unit.

REAA091

Exceeded maximum communication capacity for Ethernet Multilink devices.

The amount of communication traffic of the connected device may exceed the upper limit.

Check the traffic volume.

REAA092

Exceeded maximum number of slave connections.

The number of connected slave display units may exceed the upper limit.

Check that the number of connected slave display units is 16 or less.

REAA093

Ethernet Multilink slave cannot use this feature.

This function is not available with an Ethernet Multilink slave display unit.

An Ethernet Multilink slave display unit cannot perform this function

REAA094

Unable to communicate. Settings do not match the device/PLC configuration on the master.

The configurations of the connected devices are different between the master and slave display units.

Check the connected device configuration of the slave display unit.

REAA095

Connection failed. System Language Settings do not match.

The system language settings are different between the master and slave display units.

Set the system language setting of the slave display units to the same as that of the master display unit.

RFAA Errors

Error Code

Error Message

Cause and Troubleshooting

Browse

RFAA020

Password for send and receive is invalid.

Validation failed

Password for send and receive is incorrect.
Enter the correct Transfer operation password.

-