Connecting the DC Power Cord
DC Power Connector: Spring Clamp Terminal Blocks

Connection | Wire |
---|---|
+ | 24 Vdc |
- | 0 Vdc |
FG | Grounded terminal connection to the panel chassis. |
How to connect the DC Power Cord
- Confirm the power cord is not connected to the power supply.
- Crimp a pin terminal properly to the end of each power cable wire.
- Push the opening button with a small and flat screwdriver to open the desired pin hole.
- Insert each power cord wire into its corresponding hole.
Release the opening button to clamp the wire in place.NOTE:
-
When using stranded wire, do not short with neighboring wires.
-
When connecting with stranded wires, do not solder the stranded wires.
-
If the wire is not inserted into the FG terminal properly, touch may not respond normally.
-
Using the PE terminal is unnecessary.
-
- After inserting all three power cord wires, insert the DC power connector into the power connector on this product.
- Affix the screws on both sides of the connector.NOTE: The necessary torque is 0.5 N•m (4.4 lb-in).