Serial Interface
The serial interface is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected inside this product. When using a D-Sub serial interface connector, connect the FG wire to the shell.
You can switch the communication method between RS-232C and RS-422/ RS-485 via the software.
DANGER
|
|---|
|
ELECTRIC SHOCK AND FIRE
When using the SG terminal to connect an external device
to this product:
Failure to follow these instructions will result in death or serious injury.
|
CAUTION
|
|---|
|
LOSS OF COMMUNICATION
Failure to follow these instructions can result in injury or equipment damage.
|
RS-232C
D-Sub 9 pin plug connector
| Pin No. | RS-232C | ||
|---|---|---|---|
| Signal name | Direction | Description | |
| 1 | CD | Input | Carrier Detect |
| 2 | RD (RXD) | Input | Receive Data |
| 3 | SD (TXD) | Output | Send Data |
| 4 | ER (DTR) | Output | Data Terminal Ready |
| 5 | SG | - | Signal Ground |
| 6 | DR (DSR) | Input | Data Set Ready |
| 7 | RS (RTS) | Output | Request To Send |
| 8 | CS (CTS) | Input | Clear To Send |
| 9 | VCC | Output | +5 Vdc ±5% Output 0.25 A*1 |
| Shell | FG | - | Frame Ground (common with SG) |
*1 When using RS-232C pin #9, enable VCC with the software.
Recommended jack screw is #4-40 (UNC).
RS-422/485
D-Sub 9 pin plug connector
| Pin No. | RS-422/RS-485 | ||
|---|---|---|---|
| Signal name | Direction | Description | |
| 1 | RDA | Input | Receive Data A (+) |
| 2 | RDB | Input | Receive Data B (-) |
| 3 | SDA | Output | Send Data A (+) |
| 4 | ERA | Output | Data Terminal Ready A (+) |
| 5 | SG | - | Signal Ground |
| 6 | CSB | Input | Clear To Send B (-) |
| 7 | SDB | Output | Send Data B (-) |
| 8 | CSA | Input | Clear To Send A (+) |
| 9 | ERB | Output | Data Terminal Ready B (-) |
| Shell | FG | - | Frame Ground (common with SG) |
Recommended jack screw is #4-40 (UNC).
DANGER