ET6000-MM01-EN_02

Structural Specifications

ET-6400WA and ET-6500WA

  ET-6400WA ET-6500WA
Grounding Functional grounding: Grounding resistance of 100 Ω or less, 2 mm2 (AWG 14) or thicker wire, or your country's applicable standard.
Cooling method Natural air circulation
Structure*1 IP65
External dimensions (W x H x D) 205.5 x 150.5 x 45 mm
(8.09 x 5.92 x 1.77 in)
270.5 x 200.5 x 47 mm
(10.65 x 7.89 x 1.85 in)
Panel cut dimension (W x H) 190 x 135 mm
(7.48 x 5.31 in)*2
Panel thickness area:
1.6...5 mm (0.06...0.2 in)*3
255 x 185 mm
(10.04 x 7.28 in)*2
Panel thickness area:
1.6...5 mm (0.06...0.2 in)*3
Weight 0.61 kg (1.34 lb) or less 0.99 kg (2.18 lb) or less

ET-6600WA and ET-6700WA

  ET-6600WA ET-6700WA
Grounding Functional grounding: Grounding resistance of 100 Ω or less, 2 mm2 (AWG 14) or thicker wire, or your country's applicable standard.
Cooling method Natural air circulation
Structure*1 IP65 IP65, Type 4X (indoor use only)
External dimensions (W x H x D) 310.5 x 232.5 x 50 mm
(12.22 x 9.15 x 1.97 in)
412 x 268 x 50 mm
(16.22 x 10.55 x 1.97 in)
Panel cut dimension (W x H) 295 x 217 mm
(11.61 x 8.54 in)*2
Panel thickness area:
1.6...5 mm (0.06...0.2 in)*3
394 x 250 mm
(15.51 x 9.84 in)*2
Panel thickness area:
1.6...5 mm (0.06...0.2 in)*3
Weight 1.62 kg (3.57 lb) or less 2.52 kg (5.56 lb) or less

*1 The front face of this product, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though this product's level of resistance is equivalent to these standards, oils that should have no effect on this product can possibly harm this product. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to this product for long periods of time. If this product's front face protection sheet peels off, these conditions can lead to the ingress of oil into this product and separate protection measures are suggested. Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel's cover. Therefore, prior to installing this product, be sure to confirm the type of conditions that will be present in this product 's operating environment.

If the installation gasket is used for a long period of time, or if this product and its gasket are removed from the panel, the original level of protection cannot be kept. To maintain the original protection level, be sure to replace the installation gasket regularly.

*2 For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in) and R in angle are below R3 (R0.12 in).

*3 Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”, depending on wall’s material, size, and installation location of this product and other devices, the installation wall could warp. To prevent warping, the installation surface may need to be strengthened.

NOTICE
EQUIPMENT DAMAGE
  • Ensure this product is not in permanent and direct contact with oils.
  • Do not press on the display of this product with excessive force or with a hard object.
  • Do not press on the touch panel with a pointed object, such as the tip of a mechanical pencil or a screwdriver.
  • Do not expose the device to direct sunlight.
  • Store this product in areas where temperatures are within the product’s specifications.
Failure to follow these instructions can result in equipment damage.
NOTICE
GASKET AGING
  • Inspect the gasket periodically as required by your operating environment.
  • Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.