This shows the contents of write data in each address of the System Data Area.
When setting addresses for Parts in the System Data Area, set the data length as 16 bit.
The following table's "Word Address" column shows the Word addresses added from the System Data Area's top address in the device/PLC. (When all items are selected from the display unit's LS0000 to LS0019)
LS0000 to 0007 is the display unit→PLC write-only area, and LS0008 to 0019 is the read-only area.
Use LS0009 (screen display ON/OFF) to hide the screen. Do not use LS0014 bit 0 (bit for turning off the backlight) to hide the screen display. Although the screen display disappears because the backlight is off, there is a risk for operation error since touch operation is still enabled.
When using the IPC Series or SP5000 Series Open Box, you cannot use the Backlight OFF and screen display ON/OFF features.
When Communicating with Device/PLC with Addresses that are 16 Bits or 32 Bits Long
Display Unit Internal Address |
Word Address |
Description |
Bit |
Details |
H System Variable |
---|---|---|---|---|---|
LS0000 |
+0 |
- |
1 to 9999 (BIN) 1 to 7999 (BCD) |
||
LS0001 |
+1 |
0...1 |
Unused |
- |
|
2 |
Unused For GP-4100 Series only (excluding GP-411*T3): Backup Data Error |
||||
3 |
Screen Memory Checksum |
||||
4 |
SIO Framing |
||||
5 |
SIO Parity |
||||
6 |
SIO Overrun |
||||
7 |
Unused |
||||
8 |
Time to replace backup battery |
||||
9 |
Unused |
||||
10 |
Backup battery has run out |
||||
11 |
PLC Communication Error |
||||
12...15 |
Unused |
||||
LS0002 |
+2 |
Clock Data Current Value (Year) |
- |
Last 2 digits of year (2 BCD digits) |
|
LS0003 |
+3 |
Clock Data Current Value (Month) |
- |
01 to 12 (2 BCD digits) |
|
LS0004 |
+4 |
Clock Data Current Value (Date) |
- |
01 to 31 (2 BCD digits) |
|
LS0005 |
+5 |
Clock Data Current Value (Time) |
- |
Hours: 00 to 23, Minutes: 00 to 59 (BCD 4 digits) |
Hours: #H_CurrentHour Minutes: #H_CurrentMinute |
LS0006 |
+6 |
0...1 |
Reserved |
- |
|
2 |
Printing |
||||
3 |
Data Display Part Write Setting Value |
- |
|||
4...6 |
Reserved |
- |
|||
7 |
Another Display has a PLC monopoly during Serial Multilink |
||||
8 |
Data Display Part Input Error |
- |
|||
9 |
Display ON/OFF 0: ON, 1: OFF |
||||
10 |
Detect Backlight Burnout |
- |
|||
11...15 |
Reserved |
- |
|||
LS0007 |
+7 |
Reserved |
- |
Reserved |
- |
LS0008 |
+8 |
- |
1 to 9999 (BIN) 1 to 7999 (BCD) |
||
LS0009 |
+9 |
- |
Turn Screen Display OFF with FFFFh Display screen with 0h |
- |
|
LS0010 |
+10 |
Clock Data Preset Value (Year) |
- |
Last 2 digits of year (2 BCD digits) (Bit 15 is a flag to set clock data) |
- |
LS0011 |
+11 |
Clock Data Preset Value (Month) |
- |
01 to 12 (2 BCD digits) |
- |
LS0012 |
+12 |
Clock Data Preset Value (Date) |
- |
01 to 31 (2 BCD digits) |
- |
LS0013 |
+13 |
Clock Data Preset Value (Time) |
- |
Hours: 00 to 23, Minutes: 00 to 59 (BCD 4 digits) |
- |
LS0014 |
+14 |
0 |
Backlight OFF |
- |
|
1 |
Buzzer ON |
||||
2 |
Print Started |
||||
3 |
Reserved |
- |
|||
4 |
Enable the Buzzer Output |
||||
5 |
AUX Output |
- |
|||
6 |
Reserved |
- |
|||
7 |
PLC monopoly during Serial Multilink connection |
||||
8...10 |
Reserved |
- |
|||
11 |
Print Canceled |
||||
12...15 |
Reserved |
- |
|||
LS0015 |
+15 |
Reserved |
- |
Reserved |
- |
LS0016 |
+16 |
0 |
Window Display 0: OFF, 1: ON |
||
1 |
Change Window overlap order 0: Permitted, 1: Not permitted |
||||
2...15 |
Reserved |
||||
LS0017 |
+17 |
- |
Global Window's registration number, selected indirectly 1 to 2000 (BIN/BCD) |
||
LS0018 |
+18 |
Window Display Position (X Coordinate) |
- |
Global Window's top-left display position, selected indirectly (BIN/BCD). |
|
LS0019 |
+19 |
Window Display Position (Y Coordinate) |
- |
When communicating with device/PLC with addresses that are 32 bits long, the size of each address in the System Data Area is 32 bits. Data in the System Data Area is stored in the bottom 16 bits of each address.
1 Address Communicating with a 8-bit Device/PLC
The PLC determines the byte order (Low or High) and how data displays
Display Unit Internal Address |
Byte |
Description |
Order |
Bit |
Details |
H System Variable |
|
---|---|---|---|---|---|---|---|
Decimal |
Octal |
||||||
LS0000 |
+0 |
+0 |
|
- |
1 to 9999 (BIN) |
||
+1 |
+1 |
||||||
LS0001 |
+2 |
+2 |
Low |
0...2 |
Unused |
- |
|
3 |
Screen Memory Checksum |
||||||
4 |
SIO Framing |
||||||
5 |
SIO Parity |
||||||
6 |
SIO Overrun |
||||||
7 |
Unused |
||||||
+3 |
+3 |
High |
0 |
Time to replace backup battery |
|||
1 |
Unused |
||||||
2 |
Backup battery has run out |
||||||
3 |
PLC Communication Error |
||||||
|
|
|
4...7 |
Unused |
|||
LS0002 |
+4 |
+4 |
Clock Data Current Value (Year) |
|
- |
Last 2 digits of year (2 BCD digits) |
|
+5 |
+5 |
||||||
LS0003 |
+6 |
+6 |
Clock Data Current Value (Month) |
|
- |
01 to 12 (2 BCD digits) |
|
+7 |
+7 |
||||||
LS0004 |
+8 |
+10 |
Clock Data Current Value (Date) |
|
- |
01 to 31 (2 BCD digits) |
|
+9 |
+11 |
||||||
LS0005 |
+10 |
+12 |
Clock Data Current Value (Time) |
|
- |
Hours: 00 to 23, Minutes: 00 to 59 (BCD 4 digits) |
Hours: #H_CurrentHour Minutes: #H_CurrentMinute |
+11 |
+13 |
||||||
LS0006 |
+12 |
+14 |
Low |
0...1 |
Reserved |
- |
|
2 |
Printing |
||||||
3 |
Data Display Part |
- |
|||||
4...6 |
Reserved |
- |
|||||
7 |
Another Display has a PLC monopoly during Serial Multilink |
||||||
+13 |
+15 |
High |
0 |
Data Display Part |
- |
||
1 |
Display ON/OFF |
||||||
2 |
Detect Backlight Burnout |
- |
|||||
3...7 |
Reserved |
- |
|||||
LS0007 |
+14 |
+16 |
Reserved |
|
- |
Reserved |
- |
+15 |
+17 |
||||||
LS0008 |
+16 |
+20 |
|
- |
1 to 9999 (BIN) |
||
+17 |
+21 |
||||||
LS0009 |
+18 |
+22 |
|
- |
Turn Screen Display OFF with FFFFh |
- |
|
+19 |
+23 |
||||||
LS0010 |
+20 |
+24 |
Clock Data Preset Value (Year) |
|
- |
Last 2 digits of year (2 BCD digits) |
- |
+21 |
+25 |
||||||
LS0011 |
+22 |
+26 |
Clock Data Preset Value (Month) |
|
- |
01 to 12 (2 BCD digits) |
- |
+23 |
+27 |
||||||
LS0012 |
+24 |
+30 |
Clock Data Preset Value (Date) |
|
- |
01 to 31 (2 BCD digits) |
- |
+25 |
+31 |
||||||
LS0013 |
+26 |
+32 |
Clock Data Preset Value (Time) |
|
- |
Hours: 00 to 23, Minutes: 00 to 59 |
- |
+27 |
+33 |
||||||
LS0014 |
+28 |
+34 |
Low |
0 |
Backlight OFF |
- |
|
1 |
Buzzer |
||||||
2 |
Print Started |
||||||
3 |
Reserved |
- |
|||||
4 |
Enable the Buzzer Output |
||||||
5 |
AUX Output |
- |
|||||
6 |
Reserved |
- |
|||||
7 |
PLC monopoly during Serial Multilink connection |
||||||
+29 |
+35 |
High |
0...2 |
Reserved |
- |
||
3 |
Print Canceled |
||||||
4...7 |
Reserved |
- |
|||||
LS0015 |
+30 |
+36 |
Reserved |
|
- |
Reserved |
- |
+31 |
+37 |
||||||
LS0016 |
+32 |
+40 |
Low |
0 |
Window Display |
||
1 |
Change Window Display Order |
||||||
2...7 |
Reserved |
||||||
+33 |
+41 |
High |
0...7 |
Reserved |
|||
LS0017 |
+34 |
+42 |
|
- |
Global Window's registration number, selected indirectly 1 to 2000 (BIN/BCD) |
||
+35 |
+43 |
||||||
LS0018 |
+36 |
+44 |
Window Display Position (X Coordinate) |
|
- |
Global Window's top-left display position, selected indirectly (BIN/BCD). |
|
+37 |
+45 |
||||||
LS0019 |
+38 |
+46 |
Window Display Position (Y Coordinate) |
|
- |
||
+39 |
+47 |
Details About Each Address - System Data Area
The following example describes one address communicating with a 16-bit device/PLC.
Stores the screen number that currently displays on the display unit.
When an error occurs in the display unit, the corresponding bit turns ON. After the bit turns ON and the power turns OFF, the status is maintained until the GP changes from offline mode back to active mode.
Bit |
Bit |
Description |
Details |
---|---|---|---|
0...2 |
0...2 |
Unused |
|
3 |
3 |
Screen Memory Checksum |
There is an error in the project file. Transfer it again. |
4 |
4 |
SIO Framing |
|
5 |
5 |
SIO Parity |
|
6 |
6 |
SIO Overrun |
|
7 |
7 |
Unused |
|
8 |
0 |
Time to replace backup battery |
Display units with replacement batteries built-in are turned ON when it is time to replace the backup battery. |
9 |
1 |
Unused |
|
10 |
2 |
Backup battery has run out |
When the backup battery runs out, it is turned ON. |
11 |
3 |
PLC Communication Error |
Error in communication with device/PLC, caused by bits 4 to 6, or other cause. |
12...15 |
4...7 |
Unused |
|
Stored as BCD. [Year] is the 2 digits of the year, [Month] is 2 digits from 01 to 12, [Day] is 2 digits from 01 to 31, [Time] is 2 digits for the hours from 00 to 23, and 2 digits for the minutes from 00 to 59 for a total of 4 digits.
The current value for the day is stored in LS9310.
A.1.1.4 LS9000 Area (Direct Access Method)
Monitor only the necessary bits. Do not turn reserved bits ON/OFF because they are sometimes used for display unit system maintenance.
Bit |
Bit |
Description |
Details |
---|---|---|---|
0...1 |
0...1 |
Reserved |
- |
2 |
2 |
Printing |
Turns ON during printing. While this bit is ON, entering offline mode could disturb the output. |
3 |
3 |
Write Setting Value*1 |
This bit is reversed each time a write occurs from a Data Display (Setting Value Input). |
4...6 |
4...6 |
Reserved |
- |
7 |
7 |
Another Display has a PLC monopoly during Serial Multilink |
Turns ON when another Display has a PLC monopoly during a Serial Multilink connection. |
8 |
0 |
Data Display Part Input Error*1 |
When Alarms are set for the Data Display where you enter a value outside of the alarm range, this bit turns ON. When you input a value inside the alarm range, this bit turns OFF. |
9 |
1 |
Display ON/OFF (0: ON, 1: OFF) |
This can detect if the display unit screen display is ON or OFF from the device/PLC. This bit changes in the following cases. (1) When FFFFh is written to the System Data Area's Display ON/OFF, the display turns OFF. (2) When the standby time passes, the display turns OFF (3) If the screen changes or is touched after the display turns OFF, the display turns back ON.
|
10 |
2 |
Detect Backlight Burnout |
When an expired backlight is detected, this bit turns ON.
|
11...15 |
3...7 |
Reserved |
- |
*1 Even if you use GP-Viewer EX to operate the Data Display part, the bit does not change.
Set the Change-to Screen Number. The setup range differs depending on the [Data Type of Display Screen Numbers] option, available from the [System Settings], [Display Unit] link, in the [Display] tab's [Screen Settings] area.
Data type is Bin: 1...9999
Data type is BCD: 1...7999
To change screens from both the display unit and the device/PLC, from [System Settings] click [Display Unit], and in the [Display] tab select the [Reflect in Device/PLC] check box. When the [Reflect in Device/PLC] check box is cleared, screen change using LS0008 is not reflected to the mapped device/PLC's System Data Area [Change-To Screen] address. As a result, screen changes may not be available from the device/PLC. (Unable to return to the screen before switching)
If you are not setting the [Reflect in Device/PLC] option, design the system to clear the change screen number to zero after screens are changed.
There is a method to change screens by force when you cannot change screens from the device/PLC side.
Turn ON the top bit (forced screen change bit) in the mapped device/PLC's System Data Area [Change-To Screen] address, and use the other bits to define the change to screen number. (In other words, enter the screen number you want to display plus 8000(h) in the address.) While the force screen change bit is ON, you cannot use touch operations to change screens. However, you can use the system variable #H_ChangeScreenNo to change screens.
When the screen is changed using the device/PLC's [Change-To Screen] address, the screen change number is reflected in LS0008 regardless of the [Reflect in Device/PLC] setting.
Shows the screen when the value is "0000h" and hides the screen when the value is "FFFFh". Do not use any values except "0000h" or "FFFFh". If you touch the screen while the screen is hidden ("FFFFh" is set), although touch operations such as switches do not operate, the screen reappears ("0000h" is set).
On the following models, when the screen display is turned off (FFFFh), the display unit's status LED changes as follows.
Breathing LED
SP5000 Series (excluding eXtreme Display)
GP4000 series (excluding the GP-4100 series)
Flashes in green every 5 seconds
GPH6000 Series
When the logic program is terminated on the following models, stores "0h".
SP5000 Series
GP4000 series (excluding GP-410*)
GPH6000 Series
Set as BCD. [Year] is the 2 digits of the year, [Month] is 2 digits from 01 to 12, [Day] is 2 digits from 01 to 31, [Time] is 2 digits for the hours from 00 to 23, and 2 digits for the minutes from 00 to 59 for a total of 4 digits. The defined clock data is written by switching the data write flag (LS0010, bit 15) from OFF to ON, or from ON to OFF.
For example, 2005, October 19, 21:57
When data in the current Word Address "+10" is "0000"
Month→Write "0010" to Word Address "+11”
Day→Write "0019" to Word Address "+12”
Time→Write "2157" to Word Address "+13"
When you write "8005" to word address +10, bit 15 of address +10 turns ON, and clock data is written. For "8005," bit 15 is turned ON by the "8000" portion, while the "Year" is set with "05". (If bit 15 of word address +10 is already ON, write "0005". Bit 15 turns OFF, and the clock data is written.)
Before performing the following operation, turn OFF the most significant bit for the Year data on the device/PLC. If you perform the following operation while ON, the clock is updated.
Turn ON display unit
On the display unit, go from offline to online
Reset display unit
When using IPC Series or SP5000 Series Open Box, setting up the clock will update WinGP and the unit together.
Write to this address in bit units. In some cases, writing with word data can change the value.
"Reserved" bits are sometimes used for maintenance of the display unit system. Turn them OFF.
Bit |
Bit |
Description |
Details |
---|---|---|---|
0 |
0 |
Backlight OFF |
When ON, the backlight turns OFF. When OFF, the backlight turns ON. (Touch is enabled while backlight is off. Do not inadvertently operate parts such as switches on the screen.)
|
1 |
1 |
Buzzer*1 |
0: Do not sound, 1: Sound The buzzer is controlled in combination with Bit 4 (Enable Buzzer Output) or Bit 5 (Enable AUX Output).
|
2 |
2 |
Print Started |
0: Do not sound, 1: Sound When the bit turns ON, the printing screen data starts.
|
3 |
3 |
Reserved |
0: Fixed |
4 |
4 |
Enable the Buzzer Output*1 |
0: Output permitted, 1: Output not permitted Allow the buzzer sound of a display unit. While this bit is OFF and Bit 1 (buzzer) is ON, the buzzer will sounds from a display unit.
|
5 |
5 |
Enable AUX Output*1 |
0: Output permitted, 1: Output not permitted Allow AUX output. While this bit is OFF and Bit 1 (buzzer) is ON, the external buzzer connected to a display unit will sound.
|
6 |
6 |
Reserved |
0: Fixed |
7 |
7 |
PLC monopoly during Serial Multilink connection |
Turns ON when there is a PLC monopoly during a Serial Multilink connection. |
8...10 |
0...2 |
Reserved |
0: Fixed |
11 |
3 |
Print Canceled |
0: Sound, 1: Do not sound When the bit turns ON, all current printing is canceled.
|
12...15 |
4...7 |
Reserved |
0: Fixed |
*1 The combination of settings to control the buzzer is as follows.
System Settings [Display Unit] - [Operation] - [Touch Buzzer Sound] |
Bit 4 of Control Address (Enable Buzzer Output) |
Bit 1 of Control Address (Buzzer) |
Operations of Internal Buzzer |
---|---|---|---|
Disable |
Either ON/OFF |
Either ON/OFF |
No sound |
Enable |
OFF |
OFF |
No sound |
Enable |
OFF |
ON |
Sound |
Enable |
ON |
OFF |
No sound |
Enable |
ON |
ON |
No sound |
System Settings [Display Unit] - [Operation] - [Output to External Buzzer Terminal] |
Bit 5 of Control Address (Enable AUX Output) |
Bit 1 of Control Address (Buzzer) |
Operations of External Buzzer |
---|---|---|---|
Disable |
Either ON/OFF |
Either ON/OFF |
No sound |
Enable |
OFF |
OFF |
No sound |
Enable |
OFF |
ON |
Sound |
Enable |
ON |
OFF |
No sound |
Enable |
ON |
ON |
No sound |
Controls the window display.
12.7.2 Window - Word Action / Basic
Stores the Global Window's registration number selected indirectly: 1 to 2000 (BIN/BCD)
Stores the Global Window's top-left display position, selected indirectly. The data type is BIN or BCD.