RHAA039(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)] There are read only devices) |
|
Error Details
|
The error message [RHAA039(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)] There are read only devices)] appeared on the GP3000 screen. |
Causes
|
1. |
The device/PLC cannot recognize the write request of the address set on the GP unit. |
2. |
It may be set to request the address that is out of the PLC's address range on the GP unit. |
|
Actions
|
1. |
Change the type of the device/PLC to the one currently connected.
|
2. |
If the error occurred in all screens, check the addresses set via functions that operate in all screens, such as System Data Area, Alarm, Global D-script, Global Window and Sampling (Historical Trend Graph). |
3. |
Check the settings of the screen on which the error occurred. Check if the addresses set in the GP unit is within the PLC's address range. |
|
About error codes |
・ |
Error codes are sent from a device/PLC. Please refer to the manual of the device/PLC for the error details. |
|
|
|
|