Products
Download
Contact us
Back to Top

 FAQ

 I want to set polling cycle times for each block of alarm messages


The Polling Frequency feature allows you to set a polling cycle time to read the alarms in each block. With this feature, you can reduce the load on a display unit by setting a longer polling cycle in each block with lots of registered messages. Also, alarm data sorted into blocks can be processed efficiently by setting polling cycle times according to the level of importance.
 
 
NOTE
- Polling frequencies don't need to be different. You can set the same cycle time in all of the blocks.
- If a failure occurs reading an address due to a communication error, it will be read during the following polling cycle.
-

Alarms are not read immediately after the display unit starts up. They are read in accordance with the polling cycle set in each block.

For example, if the polling frequency of Block 1 is set to 30 minutes, monitoring addresses are checked 30 minutes after the display unit first starts up. Alarm messages cannot be checked on the display unit until then.


 
■ Setup Procedure
1. Select [Alarm] in the [Common Settings] menu.
 
2. The [Alarm] setting screen will open. Select the block where you have registered messages.
(e.g.: blocks1)
 
3. Set the [Alarm Type] to "Extended". The input field of [Polling Frequency] appears, and then set the polling frequency for this block.
 
NOTE
To expand the number of alarm messages, the Function Expansion Memory setting is required.
See I want to register more than 2048 alarm messages. (Alarm Expansion) for details.

 
4. The polling frequency can be set in each block.
Back to page top Return to the previous page
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Copyright (C) 2005- Schneider Electric Japan Holdings Ltd. All Rights Reserved.