Type C (GLC150-BG41-RSFL-24V) Specifications (End of sale: 2013/09/30)
Functional Specifications
Model (Global Code) | GLC150-BG41-RSFL-24V (PFXGLC150BDC) →Recommended Substitute | ||
---|---|---|---|
Type | Monochrome LCD | ||
Display Colors | Blue-mode | ||
Backlight | CCFL (Service life: more than 25,000 at 24 hr. operation) |
||
Resolution | 320 × 240 pixels | ||
Nominal Display Area (mm) | 115.2(W) × 86.4mm(H) | ||
Contrast Control | 8 levels of adjustment available via touch panel | ||
Language Character Sets | ASCII: (Code page 850) Alphanumeric (incl. European characters) Chinese: (GB2312-80 codes) simplified Chinese fonts Japanese: ANK 158, Kanji: 6962 (JIS Standards 1 & 2) Korean: (KSC5601 - 1992 codes) Hangul fonts Taiwanese: (Big 5 codes) traditional Chinese fonts |
||
Text | 8 × 8 Dots | 40 char. × 30 rows | |
8 × 16 Dots | 40 char. × 15 rows | ||
16 × 16 Dots | 20 char. × 15 rows | ||
32 × 32 Dots | 10 char. × 7 rows | ||
Character Sizes*1 | 8 × 8, 8 × 16, 16 × 16, 32 × 32 dots | ||
Font Sizes | Both height and width can be expanded 1, 2, 4, or 8 times | ||
Memory | Application | FLASH EPROM 1MB | |
Data Backup | SRAM 96KB - uses lithium battery*2 | ||
Control Memory | Variable Data Area | SRAM 32KB - uses lithium battery*2 (Including bit, integer, timer, counter) |
|
Program Area | FLASH EPROM 128KB | ||
Clock Accuracy | ± 65 seconds/month (at room temperature) | ||
Touch Panel | 16 × 12 keys/ screen - 1 or 2 point touch |
- The display font will differ depending on which (language) character, or which size you select.
- A Lithium battery's lifetime is:
10 years when the battery's ambient temperature is under 40℃
4.1 years when the battery's ambient temperature is under 50℃
1.5 years when the battery's ambient temperature is under 60℃
When used for backup:
Approximately 60 days, with a fully charged battery
Approximately 6 days, with a half-charged battery
General Specifications
Model (Global Code) | GLC150-BG41-RSFL-24V (PFXGLC150BDC) | ||
---|---|---|---|
Electrical | Rated Voltage | DC24V | |
Rated Voltage Range | DC20.4 to 28.8V | ||
Allowable Voltage Drop | 10 ms or less | ||
Power Consumption | 20W max. | ||
Rush Current | 30A max. | ||
Voltage Endurance | AC1000V, 10mA for up to 1 minute (between charging and FG terminals) |
||
Insulation Resistance | 20MΩ or higher at DC500V (between charging and FG terminals) |
||
Environmental | Ambient Operating Temperature*1 |
0 to 50℃ | |
Storage Temperature | -20 to 60℃ | ||
Ambient Humidity | 10 - 90% RH (non-condensing wetbulb temperature 39℃ or less) |
||
Storage Humidity | 10 - 90% RH (non-condensing wetbulb temperature 39℃ or less) |
||
Dust | 0.1mg/m3 or less (non-conductive levels) | ||
Corrosive Gasses |
Free of corrosive gases | ||
Atmospheric Endurance (Operation Altitude) |
800 to 1114hPa (2000 meters or lower) | ||
Vibration Resistance | Compatible with IEC61131-2 When vibration is NOT continuous: 10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s2 When vibration is continuous: 10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s2 X, Y, Z directions for 10 times (80min.) |
||
Noise Immunity | Noise Immunity:1500Vp-p Pulse Duration: 1µs, Rise Time: 1ns (via noise simulator) |
||
Electrostatic Discharge Immunity |
Contact discharge of 6kV (IEC 61000-4-2 Level 3) | ||
Structural | Grounding | 100Ω or less, or your country's applicable standard | |
Rating | Equivalent to IP65f (JEM1030), NEMA#250 TYPE 4X/12*2 | ||
External Dimensions (mm) |
207W × 157H × 75.8D | ||
Weight | 1.5kg (3.3lb) or less | ||
Cooling Method | Natural air circulation |
- Ensure that the temperatures both at the display surface and inside the panel are within the prescribed ambient temperature range during use. Use at temperatures outside this range may lead to malfunction.
- Limited to the front face after installation in a panel. Testing equivalent to IP65f conditions has been performed; however, performance cannot be guaranteed for every type of environment. If the product is subjected to an oil mist over an extended period of time, even when using the oil designated in the tests, or if the product is subjected to an extremely low-viscosity cutting oil, some oil penetration may result due to peeling of the front sheet. If this occurs, a countermeasure is required. The same kind of penetration, or plastic deformation, may also occur with oils other than those designated. Confirm ambient environment prior to installation. Furthermore, rubber gaskets that have been used for extended periods of time, and those that have been scratched or soiled after panel installation, may not provide sufficient protection. It is recommended that the rubber gasket be replaced periodically to ensure stable protection.
Remote I/O (FLEX NETWORK) Specifications
This I/F unit's high-speed remote I/O (6Mbps/ 12Mbps) is so fast, you won't think you are using a remote connection. Up to 1008 I/O points can be connected, with a communication delay of only 0.94ms (for 512 points at 12Mbps). The network can be extended up to 400 meters (2 channels at 6Mbps).
Communication Configuration | 1:N |
---|---|
Connection Method | Multi-Drop Connection |
Max. Distance | 200m/channel at 6Mbps, 100m/channel at 12Mbps |
Communication Method | Cyclic Time Division, half-duplex |
Communication Speed | 6Mbps/ 12Mbps (selectable) |
Communication I/F | Differential, pulse-transformer isolation |
Error Check | Format verification, bit verification, CRC-12 verification |
Max. Number of Nodes | 63 (number of occupied points varies according to I/O units) |
I/F Connector
![]() |
Pin No. | Signal Name | |
---|---|---|---|
6 | Channel 2 shield (SLD) | ||
5 | Channel 2 communication data (TR-) | ||
4 | Channel 2 communication data (TR+) | ||
3 | Channel 1 shield (SLD) | ||
2 | Channel 1 communication data (TR-) | ||
1 | Channel 1 communication data (TR+) |
Serial I/F (SIO) Specifications
Serial I/F(SIO) | Asynchronous: RS-232C/RS-422 Data Length: 7 or 8bits Stop Bit: 1 or 2bits Parity: none, odd or even Transmission Rate: 2400 to 115.2Kbps |
---|
Recommended Connector | Dsub 25-pin plug XM2A-2501 (Omron) |
---|---|
Recommended Cover | Dsub 25-pin cover XM2S-2511 (Omron) Jack Screw XM2Z-0071 (Omron) * Use M2.6 × 0.45 coarse thread screws to mount. |
Recommended Cable | CO-MA-VV-SB5P 28AWG (Hitachi Cable, ltd) |
Refer to "LT Editor V2.0 External Device Connection Manual" for external controller connection information. *PDF Manual can be downloaded from "Otasuke Pro!" |
I/O Connector Specifications
Pin | Code | Signal Name | Front View | |
---|---|---|---|---|
1 | FG | Frame ground | ![]() |
|
2 | SD | Send data (RS-232C) | ||
3 | RD | Receive data (RS-232C) | ||
4 | RS | Request send (RS-232C) | ||
5 | CS | Clear send (RS-232C) | ||
6 | NC | No connection | ||
7 | SG | Signal ground | ||
8 | CD | Carrier detect (RS-232C) | ||
9 | TRMX | Termination (RS-422) | ||
10 | RDA | Receive data A (RS-422) | ||
11 | SDA | Send data A (RS-422) | ||
12*1 | RESERVE | Reserve | ||
13*1 | RESERVE | Reserve | ||
14 | VCC | 5V ±5% output 0.25A | ||
15 | SDB | Send data B (RS-422) | ||
16 | RDB | Receive data B (RS-422) | ||
17 | NC | No connection | ||
18 | CSB | Clear send B (RS-422) | ||
19 | ERB | Enable receive B (RS-422) | ||
20 | ER | Enable receive (RS-232C) | ||
21 | CSA | Clear send A (RS-422) | ||
22 | ERA | Enable receive A (RS-422) | ||
23 | NC | No connection | ||
24 | NC | No connection | ||
25 | NC | No connection |
- Pins 12 and 13 are reserves. Do not connect anything to them.
Common I/F Specifications
Alarm Output
Contact Ratio | AC125V at 0.15A (resistive load) DC24V at 0.6A (resistive load) |
---|---|
Set Time (at 20℃) | 4ms or less |
Reset Time (at 20℃) | 4ms or less |
Min. Switching Load | 1mA/DC5V |
Initial Contact Resistance | 100mΩ or less |
Tool Connector
Tool Connector | Asynchronous: TTL level non-procedural command Connect data transfer cable for transferring data from LT Editor. |
---|
When LT Series is powered up and the system is booted, the relay of the alarm output circuit turns ON. When a major error or watchdog error occurs, this relay switch turns OFF. An external fail-safe circuit can be provided to monitor this relay output.
Note: This relay switch is OFF from the time the power is turned on until the LT Series system is booted. The external monitoring circuit must be started after the LT Seires system is booted.
A timer circuit, which recognizes a non-operating LT is required. Otherwise the alarm monitoring system should be booted up after turning on the LT power supply. |
External Dimensions
Note: Panel thickness should be between 1.6 and 5.0 mm (0.06 to 0.02 in.), and should be based on the strength required to mount the LT to the panel.