Products
Download
Contact us
Back to Top

FAQ

 "SAAF128 - 148 " Error Info

Error Code* Error Message Cause and Troubleshooting
0xC0B00280
SAAF128
-1062206848
3232760448
The destination NODE does not respond. Network connection between your port and the destination port has not been properly established. Please check the followings, and then execute Transfer or Delete again.
- The network cable is properly connected
- The destination node is ON, and
- The IP address in the Node Setting of 'Pro-Studio EX' is correct.
0xC0B00281
SAAF129
-1062206847
3232760449
Cannot judge the GP model. The specified GP Series NODE is not supported. Please disconnect the unsupported GP Series NODE. If it does not solve the problem, please install 'Pro-Server EX' again.
0xC0B00282
SAAF130
-1062206846
3232760450
Cannot execute because the 2WayDriver version is earlier than 4.50. Cannot execute the specified feature because the 2 WayDriver version of the GP Series Node is old. Please upgrade the 2 WayDriver, and then execute it again.
0xC0B00283
SAAF131
-1062206845
3232760451
Screen Capture is not supported.
0xC0B00284
SAAF132
-1062206844
3232760452
New Filing Data is not supported.
0xC0B00285
SAAF133
-1062206843
3232760453
The device cache was not found Please confirm that a cache buffer has been generated under the device cache name you specified. Also, please confirm that the device cache name is correct.
0xC0B00286
SAAF134
-1062206842
3232760454
The device cache already has been already registered. Please confirm that no cache buffer with the same device cache name has been generated. Also, please confirm that the device cache name is correct.
0xC0B00287
SAAF135
-1062206841
3232760455
The provided device-cache handle is invalid. Please confirm that the handle is correct.
0xC0B00288
SAAF136
-1062206840
3232760456
The no. of device caches exceeds the limit. The max number of cache buffers is 1000. No more can be registered. If you want to register another cache buffer, please reduce the number of already registered ones.
0xC0B00289
SAAF137
-1062206839
3232760457
The no. of device cache records exceeds the limit. Please register the record in another cache buffer. Or please reduce the number of records.
0xC0B0028A
SAAF138
-1062206838
3232760458
The device cache size exceeds the limit. Please register the record in another cache buffer. Or please reduce the total number of bytes.
0xC0B0028B
SAAF139
-1062206837
3232760459
Could not execute because the device cache was in processing. Before you register a record in a cache buffer, please be sure that cache action is not in execution.
0xC0B0028E
SAAF142
-1062206834
3232760462
Invalid Transfer Password The transfer password you entered is not the same as the one set in the GP3000 Series Node. Please enter the correct password, and try Transfer again. If you forget your transfer password, using 'GP-Pro EX', please configure it again. Or please use 'GP-Pro EX' to delete the transfer password in the GP3000 Series Node.
0xC0B0028F
SAAF143
-1062206833
3232760463
Transfer failed. Please try Transfer again. If you still cannot transfer, please forcibly transfer the project file to the GP3000 Series Node using 'GP-Pro EX', and then transfer the network project file using 'Pro-Studio EX'.
0xC0B00290
SAAF144
-1062206832
3232760464
Cannot connect to the destination NODE. The GP3000 Series Node is now in transfer mode. Please try Transfer again after a while, or after powering the GP3000 Series Node off and then on.
0xC0B00294
SAAF148
-1062206828
3232760468
Failed to recognize the destination main unit. Please confirm whether the model is supported by Pro-Studio EX. Please confirm whether the destination is supported by 'Pro-Studio EX'.

  * - 1st line: Error code
  2nd line: Integrated error code
  3rd line: Error code with decimal code
  4th line: Error code without decimal code

Back to page top <--Returns to the previous page