 "SAAF031 - 057 " Error Info

Error Code* Error Message Cause and Troubleshooting
0xC0B0021F
SAAF031
-1062206945
3232760351
The API was redundantly called. The specified access handle for Pro-Server EX is already running. If there is the necessity of calling the API at the same time, please use another Pro-server handle. Or, please consider using EasySetWaitType() or EasySetWaitTypeM() to avoid calling the API at the same time.
0xC0B00220
SAAF032
-1062206944
3232760352
In data-type conversion, the data type of the conversion source/destination is unsupported. Please check the contents of the Variant type.
0xC0B00221
SAAF033
-1062206943
3232760353
The specified backup-data type is unsupported. Please check the data type specification.
0xC0B00222
SAAF034
-1062206942
3232760354
Failed to open the SRAM backup data file or to create its copy in the PC. Please check the specifications of the destination file/folder in the PC, disk space, and the access right to the file etc.
0xC0B00223
SAAF035
-1062206941
3232760355
In Read/Write Backup Data, failed to access the file. In reading or writing SRAM Backup Data, an error occurred accessing the specified file. Please check the free space of the PC and the file access right, and then execute it again.
0xC0B00224
SAAF036
-1062206940
3232760356
In Write SRAM Backup Data, the specified file size is too large. It must be 96KB or less. Please confirm that the file specified in Write SRAM Backup Data is correct. Also, please specify a file of the size of 96Kbytes or less.
0xC0B00225
SAAF037
-1062206939
3232760357
Numeric value error. Please set a correct value. Please confirm that the string is valid as a numeric value.
0xC0B00226
SAAF038
-1062206938
3232760358
The specified data count is 0 or out of range. Please check the data count.
0xC0B00227
SAAF039
-1062206937
3232760359
The max number of access destinations is too high (It must be 1500 or less). Please consider dividing it for successful access.
0xC0B00228
SAAF040
-1062206936
3232760360
The total buffer size of the data to access is too high. (It must be 1MB or less.)
0xC0B00230
SAAF048
-1062206928
3232760368
Cannot start Pro-Server EX. Please reboot your PC. If it does not solve the problem, please install 'Pro-Server EX' again.
0xC0B00231
SAAF049
-1062206927
3232760369
Cannot start Pro-Studio EX.
0xC0B00232
SAAF050
-1062206926
3232760370
Cannot start the device monitor.
0xC0B00233
SAAF051
-1062206925
3232760371
Cannot start the symbol monitor. Please reboot your PC. If it does not solve the problem, please install 'Pro-Server EX' again.
0xC0B00234
SAAF052
-1062206924
3232760372
Cannot start the status monitor.
0xC0B00235
SAAF053
-1062206923
3232760373
Cannot start the log viewer.
0xC0B00236
SAAF054
-1062206922
3232760374
Cannot start the device access log.
0xC0B00237
SAAF055
-1062206921
3232760375
Cannot read backup data from the specified NODE. A Pro-Server EX node is specified. Read Backup Data is available only when the target is a GP3000 Series node or a GP Series node. Please specify a GP3000/GP Series node.
0xC0B00238
SAAF056
-1062206920
3232760376
Reading out logging data from a GP3000 Series NODE is not allowed. Please change the setting not to execute Read Logging Data when the target is a GP3000 Series Node.
0xC0B00239
SAAF057
-1062206919
3232760377
Reading out trend data from a GP3000 Series NODE is not allowed. Please change the setting not to execute Read Trend Data when the target is a GP3000 Series Node.

  * - 1st line: Error code
  2nd line: Integrated error code
  3rd line: Error code with decimal code
  4th line: Error code without decimal code

Back to page top <--Returns to the previous page