Error Code* Error Message Cause and Troubleshooting
0xC0A10001
REAA001
-1063190527
3231776769
Failed to read the device set in the "Transfer Source" of the "Action/Data Transfer (XX)". (XX: Action/Data Transfer Name) Failed to read the device specified as "Transfer from". Please confirm the device set in "Action/Data Transfer" of Pro-Studio EX.
0xC0A10002
REAA002
-1063190526
3231776770
Failed to write the device set in the "Transfer Source" of the "Action/Data Transfer (XX)". (XX: Action/Data Transfer Name) Failed to write the device specified as "Transfer to". Please confirm the device set in "Action/Data Transfer" of Pro-Studio EX.
0xC0A10003
REAA003
-1063190525
3231776771
Could not store the IP address of the node where the error occurred. (Trigger Condition: XX) (XX: Trigger condition name) Could not store the IP address of the abnormal node. Please confirm "Save Abnormal IP Address in" set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10004
REAA004
-1063190524
3231776772
Could not store the error code (Trigger Condition: XX) (XX: Trigger condition name) Could not store the error code. Please confirm "Save Error Code in" set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10005
REAA005
-1063190523
3231776773
Could not write the "Processing Result Success-or-Failure Bit" (Trigger Condition: XX) (XX: Trigger condition name) Failed to write the "Processing Result Success-or-Failure Bit". Please confirm "Bit Showing Processing Result (Success/Failure)" set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10006
REAA006
-1063190522
3231776774
Could not write the "Processing Completion Bit" (Trigger Condition: XX) (XX: Trigger condition name) Failed to write the "Processing Completion Bit". Please confirm "Processing Completion Bit" set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10007
REAA007
-1063190521
3231776775
Could not clear the "Trigger Condition device" (Trigger Condition: XX) (XX: Trigger condition name) Failed to clear the "Trigger Condition Device". Please confirm the device set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10008
REAA008
-1063190520
3231776776
Could not read the "Trigger Condition device" (Trigger Condition: XX) (XX: Trigger condition name) Failed to read the "Trigger Condition Device". Please confirm the device set in the screen of "Set Trigger Condition Details" of 'Pro-Studio EX'.
0xC0A10009
REAA009
-1063190519
3231776777
Could not write the "Receive Notification Device" (Action/Data Transfer: XX) (XX: Action/Data Transfer name)
Failed to write to the "Receive Notification Device". Please confirm "Receive Notification Device" set in the screen of "ACTION Node/Process Completion Notification Settings" of 'Pro-Studio EX'.
0xC0A10010
REAA016
-1063190512
3231776784
Could not use the XX port (No: XX). (XX: Part name/No.) Could not use Port %s (No.: %u). The system port no. may already be used.
0xC0A10011
REAA017
-1063190511
3231776785
Attempted to access a write-protect area (XX) (XX: Device name) Cannot write to Write Inhibit Area (LS0000-LS0019, LS2032-LS2095, LS9000-LS9999) via D-Script or Network.
0xC0A10012
REAA018
-1063190510
3231776786
Attempted to access a device outside the address range (XX) (XX: Device name) Attempted to access an out-of-range device.
0xC0A10015
REAA021
-1063190507
3231776789
An invalid ID (Node, Device, Address) has been specified. An invalid ID was specified. Attempted to access a nonexistent device. An invalid ID was specified. Attempted to access a nonexistent device.
0xC0A10016
REAA022
-1063190506
3231776790
An invalid ID (Node, Device, Address) has been specified.
0xC0A1001A
REAA026
-1063190502
3231776794
Illegal/Undefined Device Address An invalid device was specified. Attempted to access a nonexistent device.
0xC0A1001B
REAA027
-1063190501
3231776795
Illegal/Undefined Device Address
0xC0A1001C
REAA028
-1063190500
3231776796
Illegal/Undefined Device Address

  * - 1st line: Error code
  2nd line: Integrated error code
  3rd line: Error code with decimal code
  4th line: Error code without decimal code

Back to page top --> Returns to the previous page
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Copyright (C) 2005- Schneider Electric Japan Holdings Ltd. All Rights Reserved.