  Frist round For creating an alarm screen
 2.Let us actually draw a picture !
 1-4) Place Q tag
 
1.In Project Manager, click [Screen].
 
2.Create a base screen and select the icon, of [Q tag].
 
3.The [Q tag Settings] dialog box will appear. Select the [Display Mode] tab.
 
4.Select [Display Mode]. Select [History] for this time.
Active
The currently triggered alarms only display. The restored alarm is automatically deleted.
History
The messages display in the order of the triggered. Also each alarm message can be displayed with time of [Trigger], [Acknowledge], and [Recover].
Log
Every time there's a change like [Trigger], [Acknowledge], and [Recover], a message displays. In addition to it, the time of [Trigger], [Acknowledge], and [Recover] can be displayed.
 
5. In [Display Format], set [No. of Display Char.], [Line Start], [No. of Display Lines], and [Line Spacing] as you like.
No. of Display Char.
Set the number of the characters displayed with Q tag. Set the number of characters in a single byte.
Line Start
Set from which line alarm messages display. [1] will be fine normally.
No. of Display Lines
Set the number of lines displayed with Q tag.
Line Spacing
Set the line space by a dot.
 
6.Select [Scroll Direction] as you like.
Up
Alarm messages display from the bottom and the older message is scrolled up. The latest alarm message always displays at the bottom.
Down
Alarm messages display from the top and the older message is scrolled down. The latest alarm message always displays on top.
 
7. [Default Sorting Order] and [Border Type] can be selected only when [Extended Function] is used in C-Package03.As for the details, refer to (Application)
 
8.Click the [Display Format] tab.
 
9. Select [Common] or [Individually] and set [Date], [Messages] etc. by a single byte. Select [Individually] for this time.
The [Sample] window appears at the bottom of the screen. Referring to this, set the display positions of each item.
Memo
  •How to set Q tag Display Format
  Set the value in a single byte for the space from the start of Q tag to each item.For example, when the value of [Trigger] is [11] and the value of [Messages] is [17], the triggered time displays after 11-character space from the start and the messages display after 17-character space from the start.
     
   
     
  For non-display item, set OFF for the check box. When using C-Package02 or before, set [0] for the No. of char. (For C-Package02 or before, the check box does not display)
 
10.Select the format for [Date] and [Time].
 
11.Next, select the [Size/Color] tab.
 
12.Set [Display Size].
 
13.Set the thickness of the cursor displayed in Q tag for [Cursor Size].
 
14.Set colors of displayed alarm messages and [Erase Color] as you like.
How to set colors of alarm messages
 
   
[About setting [Erase Color]
  In [Erase Color], set the color of the area where no message displays in Q tag Area.
 
 
15.Click [OK], and place Q tag on the base screen.
Memo
  The squares and the item names displayed in Q tag after placing Q tag are not displayed on GP.
   
  Therefore it's required to draw the item names as you like beforehand by using Drawing
   
  As for [Border], using [Extended Function] of C-Package03 allows the following two kinds of display
As for the details, refer to (Application)
   
 
[[When drawing a line in Q tag,]   [Placing an external frame]
 
   
  1-3 Register Alarm Messages   Procedure Document List   1-5 Place Q tag selection key  
 