Compatibility
About the performance when display area of the system window is overlapping

As a major example, the message banner feature of the Alarm part is one of the system windows.

GP-PRO/PB3 allows switches, which are placed behind the message banner, to be activated even while an Alarm message is running. However, GP-Pro EX does not.
To activate switches on the bottom of the screen even while an Alarm message is running, re-edit the screen not to overlap the message banner display area on the switches.
The switch function overlapped by the error display or Japanese FEP, which is also a system window, is not activated as well. For the GP2000 series, the switch function placed under the message banner responds during the operation of the message banner of Alarm. However, for GP3000 series, when the message banner is running, the switch function placed under it does not respond.
To have the switch on the bottom of the screen operate even when the message banner is running, re-edit is required to avoid the overlap with the display area of the message banner.

In the same way, the switch function overlapping with the system window like Error Display or Japanese FEP does not respond.