RHAA085(Node Name): Too many request to read. The request was ignored. |
 |
 |
Error Details
|
The error message [RHAA085(Node Name): Too many requests to read. The request was ignored.] appeared on the GP3000 screen. |
Causes
|
A read operation was continued at timing which exceeds the processing speed of the communication driver.
Example: When a read operation from a connected device set up with a baud rate of 9600 is continued according to the update timing of the tag scan counter. |
Actions
|
Check if a D-script or other setting has been specified which continues reading at fast speed.
This error may occur when reading from a device which communicates at a low speed such as 9600 bps is continued with a D-script using a bit which turns ON/OFF at fast speed (such as the LS9400 tag scan counter). |
|
|
|