RHAA052(Node Name): Out of range devices exist in write devices (Address: (Device Address)) |
 |
Error Details
|
The error message [RHAA052(Node Name): Out of range devices exist in write devices (Address: (Device Address))] appeared on the GP3000 screen. |
Causes
|
When more than 2 addresses are set on a Text Display or D-script, etc., the end address may be set out of the address range even though the start address is set within the range. |
Actions
|
1. |
Check the addresses used on the screen on which the error occurred.
Check if the addresses set on a Text Display or D-script are within the address range. |
2. |
If the error occurred in all screens, check the addresses set via functions that operate in all screens such as Global D-script and Extended Script. |
|
What is the Global D-script? |
・ |
The Global D-script is one of the programming functions that a touch panel has. With this function, all screens in the project file can be programmed by one D-script. |
|
|
|
|