 RGE*008_Units count over limit.

Error Description

The error message [RGE*008_Units count over limit.] appeared on the GP3000 screen.

Cause
The Flex Network unit S-No. may be set exceeding "63."


Solution
Perform Error Check and check the I/O Driver settings. Then transfer the project file again.

How to perform Error Check
1. Confirm [Error Check] from the [Work Space] on the [View] menu is checked. If it is not, check it.



2. In the [Error Check] window, click [Logic only] to perform error check in the logic program.



How to check the I/O Driver settings
1. Open the System Settings window and click [I/O Driver].



2. In the I/O Driver window, check if the unit S-No. exceeds 63. If it does, change the number up to 63.



NOTE
The number of the occupied stations are depending on the Flex Network unit model.
For example, if you use a unit whose number of the occupied station is 2 and define S-No 1, S-No 1 and S-No 2 will be occupied.
Numbers of stations of each unit are listed below.
Type
Model
No. of Occupied Stations
I/O Unit
FN-X16TS41
1
FN-X32TS41
2
FN-Y16SK41
1
FN-Y16SC41
1
FN-XY08TS41
1
FN-XY16SK41
1
FN-XY16SC41
1
FN-XY32SKS41
4
FN-Y08RL41
1
Analog Unit
FN-AD02AH41
1
FN-DA02AH41
1
FN-AD04AH11
4
FN-DA04AH11
4
Single-Axis Positioning Unit
FN-PC10SK41
4
High-Speed Counter Unit
FN-HC10SK41
8