 RGE*007_Units config overlapped.

Error Description
The error message [RGE*007_Units config overlapped.] appeared on the GP3000 screen.

Cause
The Flex Network unit S-No. may be overlapped.

Solution
Perform Error Check and check the I/O Driver settings. Then transfer the project file again.
How to perform Error Check
1. Confirm [Error Check] from the [Work Space] on the [View] menu is checked. If it is not, check it.



2. In the [Error Check] window, click [Logic Only] to perform error check in the logic program.

How to check the I/O Driver settings
1. Open the System Settings window and click [I/O Driver].

2. In the I/O Driver settings window, check if the S-No is not overlapped. if it is, please change the setting not to overlap.


NOTE
16 points occupy 1 station;
If you use a unit with 16 inputs/16 outputs (total: 32 points), 2 stations will be occupied. (If you define S-No 1, S-No 1 and S-No 2 will be occupied.)