  Toyota Machine Works

Host Communication Error [02:**]
02->a fixed value**->refer to the table below.

Error Code
Description
Cause or Measures
00 Correctly finished  
01 Command Format error  
03 Address Set error The designated address of tag is out of range.
05 No. of transfer error  
06 TOYOPUC-PC1 unit error Check TOYOPUC-PC1 unit
09 Tried to write while sequence program is performing  
0A Parity error Noise in data transmission line.
0D Sum Check error Noise in data transmission line.
0E Write Protect  
13 CPU error The setting of Module Link No. is beyond 1 to 3.(TOYOPUC-PC1)
Link Parameter setting error (TOYOPUC-L2/PC2)
The connection between the module and the CPU board is not perfect.
The cable connecting the module to the CPU board is cut off.
The CPU error, the module error
14 Unable to exchange data between the link module and PC1. The sequence program stops by HLT command when the power turns on.
The connection between the module and the CPU board is not perfect.
The cable connecting the module to the CPU board is cut off.
15 PC1 doesn’t execute sequence by STA command Scanning Stop command is being output from the peripheral units like a program.
 
1C System Memory error The memory device of the module has an error
20 Undefined command  
21 L2/PC1 CPU resetting now CPU Reset inputting now
31 Tried to write while sequence program is performing.  
32 Scanning Stop command is being output from the peripheral units like a program. Release the scanning stop command from the peripheral units.
34 READ/WRITE of the sequence program and the attendant information is forbidden.  
 
35 No right to execute Release the setting of limitation in the unit restricting the right to execute
 
 
36 The right to execute has been already limited. Release the setting of limitation in the unit restricting the right to execute
38 Unable to write because the memory card is selected. Have CPU run via CPU memory
39 The parameter for I/O allocation changed. Reset and start CPU.
3C Hard error of CPU Check CPU.
3D Conflict with other factors  
3F No device of Timer, Counter The device address appointed in Timer, Counter etc. doesn’t exist in the sequence program.
*As to other errors, refer to a manual of a PLC manufacturer.
 
Error Code
Description
Causes
Countermeasures
FD
Data reception error Cable was disconnected while the machine is turned ON.  
FE
Data reception time out Incorrect PLC settings.
- Check the PLC type used for the editor software.
- Check all data transmission settings, installation, And wiring conditions.
PLC’s power is not turned ON.
Incorrect cable connection or wiring.
Incorrect data transmission settings.
FF
Data transfer time out Incorrect cable connection or incorrect data transmission settings.
- Check the data transmission settings, installation and wiring conditions.
The GP’s cable has not been connected.