Products
Download
Contact us
Back to Top
Otasuke FAQ's Book
  OMRON

Host Communication Error [02:**]
02->a fixed value**->refer to the table below.

Error Code
Description
Cause or Measures
00
Correctly finished GP entered simulation mode while connected to the PLC.
01
Unable to execute in RUN mode PLC’s protocol was used to force the GP to RUN mode.
02
Unable to execute in monitor mode  
03
Unable to execute in P-ROM  
04
Address Over (limit)  
05
Unable to execute in program mode  
0B
Unable to execute in debugging mode  
0C
Unable to execute in stand-by mode C2000(H) has been set to stand-by mode.
0D
Unable toexecute in local mode The LK201-V1 mode control switch is set to Local.
10
Parity error Noise in data transmission line.
11
Framing error Noise in data transmission line.
12
Overrun error Reduce the baud rate.
13
FCS error Noise in data transmission line.
14
Format error  
15
Entered/Registered data error Designated device does not exist in the PLC.
16
Unused command  
18
Frame length over max error  
19
Cannot perform The CPU unit is malfunctioning.
20
Cannot create I/O table  
21
Unable to perform due toPC CPU’s malfunction Turn the PC’s power OFF and then ON again.
22
No applicable memory  
23
Applicable memory is protected.  
A0 - A8
Data transfer error  
B0
Unable to execute because the program area is more than 16KB. Extension DM is used.
*As to other errors, refer to a manual of a PLC manufacturer.
 
Error Code
Description
Causes
FA Address Range Error Addresses are set out of the range of usable devices.
F7 Connection Error The connected wiring is incorrect.
The choice of System Settings (232C/4-wire type/2-wire type) is incorrect.
F8 Communication Information Address is incorrect. GP’s Network Information Address varies depending on a GP -> Make all GP network addresses the same.
F9 Station numbers overlap. GP’s station numbers overlap.
GP power supply is turned OFF during communication.
FD Receive Data Error The choice of PLC type via the software is incorrect.
GP power supply is turned OFF during communication.
Noise influence (when an error occurs sometimes)
FE Not responding PLC power supply is OFF.
The choice of PLC type via the software is incorrect.
System Settings (of GP side and PLC side) don’t match.
The connected wiring is incorrect.
Noise influence (when an error occurs sometimes)
FF Connection Error The connected wiring is incorrect.
The choice of System Settings (232C/4-wire type/2-wire type) is incorrect.


Return to Top Close
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Copyright (C) 2005- Schneider Electric Japan Holdings Ltd. All Rights Reserved.