Host Communication Error [02:**]
02 -> a fixed value, ** -> refer to the table below.

MELSEC-F2 series
Error Code
Description
Cause or Measures
00
Sum Data is not right.  
01
Not set parity  
02
Set Communication Specs Error  
04
Codes except character codes exist.  
05
Wrong Command  
06
During PC RUN, commands cannot perform.  
07
Other errors  
*As to other errors, refer to a manual of a PLC manufacturer.
 
MELSEC-FX/F2 series
Error Code
Description
Causes
Countermeasures
FD
Data reception error Cable was disconnected while the machine is turned ON.  
FE
Data reception time out Incorrect PLC settings, or PLC’s power is not turned ON.
- Check the PLC type used for the editor software.
- Check all data transmission settings, installation, And wiring conditions.
Incorrect cable connection or wiring.
Incorrect data transmission settings.
FF
Data transfer time out The GP’s cable has not been connected.
- Check the data transmission settings, installation and wiring conditions.
Incorrect cable connection or incorrect data transmission settings.