Communication Format and Flow Control
When using the PE-4000B, set up the communication format and flow control in the unit's BIOS settings. (The communication format and flow control settings defined in GP-Pro EX will be ignored.)
In the BIOS, from the [Advanced] menu's [SCH3106 Second Super IO Configuration], configure [SIO2 COM* Mode] (the asterisk * represents a number 3 to 6) and [Auto Flow Control] to match your communication format. |
|
|
|
Communication Format |
RS-232C |
RS-422/485
(2-wire) |
RS-422/485
(4-wire) |
SIO2 COM* Mode |
RS-232C |
RS-485 |
RS-422 |
Auto Flow Control |
Disable |
Enable |
Enable *1 |
|
|
*1 When using RS-422/485 (4-wire) with any of the following drivers, you need to set Auto Flow Control to Disable.
- GE Fanuc Power Mate Series
- GE Intelligent Platforms Series 90-30/70 SNP
- GE Intelligent Platforms Series 90-30/70 SNP-X
- Keyence KV Series CPU Direct
- Keyence KV-700/1000/3000/5000 CPU Direct
|
|
|
|
MEMO |
- Set up the timeout, retries, and send wait time in GP-Pro EX.
- When connecting the PE4000B series to external devices, the communication settings differ from one device to the next. For details about your device/PLC, please refer to its associated manual.
|
|