GP-Pro EX:Important Notification for Users of OMRON C/CV/α series
Posted: 2009, February 10
Thank you very much for your continuous use of Pro-face products.
We have confirmed that the following symptom has been seen in GP-Pro EX.
The symptom for this problem are indicated below.
We sincerely apologize for any inconvenience this may cause you.
Symptom description
When the PLC of OMRON C/CV/α series is in operation in "Program Mode" and GP-Pro EX is set to permit "Change to Monitor Mode", the PLC mode is changed to the "Monitor Mode" when you turn on the power with a display unit connected
(We confirmed that this symptom does not occur in other PLC products.)
Applicable version
- Before GP-Pro EX Ver.2.22.000
- Before OMRON C/CV series Hot Link driver V1.11.03
Measures
This symptom can be worked around by updating the GP-Pro EX Hot Link driver to the latest version (V1.11.04) and then transferring to a main unit, executing the following.
Obtain Update module from the download site in our homepage *1and update GP-Pro EX
- Membership registration (free) of our support site "Otasuke Pro!" is needed.