GP2000 Series
   About the products for the abolition of UL1604 standard

GP2301-TC41-24V Specifications (End of Sale: 2012/6/29)

Functional Specifications

ModelGP2301-TC41-24V
Recommended Substitute
Type TFT Color LCD
Display Colors 256 colors (no blink)/ 64 colors (3-speed blink)*1
Backlight CCFL (Service life: more than 50,000 at 24 hr. operation)
Resolution 320 × 240 pixels
Effective Display Area (mm) 115.2(W) × 86.4(H)
Brightness Control 4 levels of adjustment available via touch panel
Contrast Control -
Language Character Sets ASCII: (Code page 850) Alphanumeric (incl. European characters)
Chinese: (GB2312-80 codes) simplified Chinese fonts
Japanese: ANK 158, Kanji : 6962 (JIS Standards 1 & 2)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) traditional Chinese fonts
Text8 × 8 dots 40 char. × 30 rows
8 × 16 dots 40 char. × 15 rows
16 × 16 dots 20 char. × 15 rows
32 × 32 dots 10 char. × 7 rows
Character Sizes*2 8 × 8 dots, 8 × 16 dots, 16 × 16 dots, 32 × 32 dots
Font Sizes Width can be expanded 1 to 8 times.
Height can be expanded 1/2*3, 1 to 8 times.
Application Memory FLASH EPROM 1MB
Data Backup Memory 128KB SRAM - uses lithium battery*4
Touch Panel Resolution 6 x 12 keys/ screen - 1 or 2 point touch
External InterfaceSerial Interface Asynchronous Transmission methods: RS-232C/RS-422,
Data Length 8/7 bits, Stop Bit 2/1 bits,
Parity: None,Odd or Even,
Transmission Speed: 2400bps to 115.2Kbps, 187.5Kbps*5
CF Card Interface 1 Slot
Tool Connector Asynchronous TTL level nonprocedure command I/F

Used for transferring data between the GP application software and the GP.
Used for data transfer with the 2-Port feature.

Used for a variety of devices, including a bar-code reader.
  1. Changing the "Colors" setting to "256 colors" will disable the blink feature on all your project screens. If you wish to use the blink feature, do not change this setting to "256 colors."
  2. The display font will differ depending on which (language) character, or which size you select.
  3. Only available when using "1/2 Byte Character" settings via software. (Only Japanese, Chinese, Taiwanese and Korean characters.)
  4. A Lithium battery's lifetime is:
    10 years when the battery's ambient temperature is under 40℃
    4.1 years when the battery's ambient temperature is under 50℃
    1.5 years when the battery's ambient temperature is under 60℃
    When used for backup:
    Approximately 60 days, with a fully charged battery
    Approximately 6 days, with a half-charged battery
  5. SIEMENS SIMATIC S7-200/300/400 series (MPI port only). Please contact your Pro-face sales representative for supported models and other details.

General Specifications

ModelGP2301-TC41-24V
Recommended Substitute
ElectricalRated Voltage DC24V
Rated Voltage Range DC19.2 to 28.8V
Power Consumption 22W or less
Allowable Voltage Drop 10ms or less
Voltage Endurance AC1,000V 20mA for 1 minute
(between charging and FG terminals)
Insulation Resistance 20MΩ or more at DC500V
(between charging and FG terminals)
EnvironmentalAmbient Operating Temperature*1 0 to 50℃
Storage Temperature -20 to 60℃
Ambient Humidity 10 to 90% RH
(non-condensing wetbulb temperature 39℃ or less)
Storage Humidity 10 to 90% RH
(non-condensing wetbulb temperature 39℃ or less)
Vibration Resistance Compatible with IEC61131-2
When vibration is NOT continuous:
10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s2
When vibration is continuous:
10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s2
X, Y, Z directions for 10 times (80min.)
Noise Immunity Noise Immunity: 1000Vp-p
Pulse Duration: 1µs, Rise Time: 1ns
(via noise simulator)
Electrostatic Discharge Immunity 6kV (complies with IEC 61000-4-2 Level 3)
Corrosive Gasses Free of corrosive gasses
StructuralGrounding 100Ω or less, or your country's applicable standard
Ratings Equivalent to IP65f (JEM1030), NEMA#250 TYPE 4X/12*2
External Dimensions (mm) 171W × 138H × 60D
Weight 1.2kg (2.6lb) or less
Cooling Method Natural air circulation
  1. When installing the GP in a cabinet or enclosure, the term “ambient operation temperature” indicates the cabinet or enclosure’s internal temperature.
    The LCD displays may occasionally blur when they are used for hours at over 40℃ ambient operating temperature. This is a temporary phenomenon. After the temperature returns to normal, the display will be restored to normal. The GP's operation will not be affected even though the display is blurred.
  2. The degree of protection provided by these products is equivalent to IP65f, however their performance cannot be guaranteed for every environment. Be sure to confirm your work environment requirements prior to installation.

Dimensions

GP2301-TC41-24V 外形寸法図