Important notice to our valued customers who use Logic retentive variable in the logic program of GP-Pro EX
Last updated: 2012, Feb. 23
Posted: 2011, Dec. 20
Thank you very much for your continuous use of Pro-face products.
We have confirmed that the following symptom occurs in some models of GP-Pro EX.
The symptom for this problem are indicated below.
We sincerely apologize for any inconvenience this may cause you.
Symptom Descriptions
After a screen project is transferred, logic retentive variables value is cleared.
Occurrence Conditions: When meeting all the following conditions, the symptom happens.
- Transfer Project [Automatic]
- Retain Retentive Variables [Effective]
- Ransfer System [Automatic]
2. The run time version less than GP-Pro EX Ver. 3.00.
Applicable Combination of Products
Product model: | PFXEXEDV30 |
---|---|
Applicable version: | GP-Pro EX Ver. 3.00.000 |
How to check the version: | [Help(H)] → [About this program(A)] |
Applicable models of Graphic Operator Interfaces:
Series | Model Number |
---|---|
GP3000 Series | All the model numbers (except for Handy Type) |
LT3000 Series | All the model numbers |
Measures
A fixed version (Ver. 3.01.101) was already uploaded to our website.
-> GP-Pro EX Ver. 3.01.101 Update Module
* To download the module, free member registration for “Otasuke Pro!” is required. Click here to register.
Inquiry
If you have any inquiries, please contact our sales office in your region.
For contact information, please refer to the "Inquiry" page.