Is the logic program running?
Cause
If the status LED is flashing in green in logic execution mode, the logic program may have stopped.
When displaying a screen that uses animation or other to cause a heavy load, the flashing cycle for the green LED may be irregular.
Solution
When the logic program is not required
Disable the logic program according to the following procedure.
When performing with GP-Pro EX
Select [Logic Programs] from [System Settings] and select [Disable]. Transfer the project file to the Display.
When performing with the Display Unit
Select [Off] in [Logic Program] from [Logic]. Save the setting and then exit offline mode.
M.24.2.1 Main Unit - Logic Settings
When the logic program is required
Run the logic program according to the following procedure.
When performing with GP-Pro EX
Select [Display Unit] from [System Settings]. In the [Logic] tab, set [Logic Program Operation] to [RUN]. Transfer the project file to the Display. Transfer the file to the Display unit.
When performing with the Display Unit
In offline mode, select [Main Unit], [Logic]. Set [Logic Program] to [RUN]. Save the setting and then exit offline mode.
M.24.2.1 Main Unit - Logic Settings