Restrictions

What are restrictions for Server?
Restrictions for Server are as follows;

No. Description
1 D-Script and Trigger Action are also operated on an Asynchronous Mode screen. When the same screen is displayed between the Display side and the client side in Asynchronous Mode, operation can be made in the both screens of the Display and the client, respectively.
Take note of it when you design a screen on the Display side.
2 Text and picture for which Blink is set in the server are not displayed in blinking in the client.
3 Reverse Display in 16 Level Monochrome color mode is not supported.
4 Display is made in the client even in Standby Mode (Display: OFF). At this time, the touch operation from the client is only to turn ON the display of the Display unit. After the display is turned ON, touch operation can be performed as usual.
5 MOV touch operation does not work
6 Offline About the "Touch Panel" check "Calibration" "LAN" "Maintenance", you cannot touch because they do not come back from the screen is pressed after the move. 
7 Operation Log records operations from the client side as well. But there's no way of distinguishing operations from the client side from those on the Display side.
8 When the system variable (#H_ChangeScreenNo) or "Change-To Screen Number" in the system data area is changed in Asynchronous Mode, a screen on the Display side is switched but a screen on the client side is not switched.
9 Client operates in the security level 15 in Asynchronous Mode. Therefore, shift can be made to a screen with the security level settings without inputting a password. Connection of the client in accordance with the level can be controlled using the system variable (#H_RemoteHMI_DisableConnections).
10 In Asynchronous Mode, neither a user window nor a system keypad can be displayed.
11 When a system menu is displayed in Asynchronous Mode, the system menu is displayed on both the Display side and the client side. However, operation using other switches than the up-down movement switch and the Close switch is disabled from the client side.
12 If the network is disconnected, if the Client has terminated the app in the monitoring, or you may experience the following symptoms:.
While the server is connected to the client is maintained for 30 seconds.
[Asynchronous mode]
(Such as scripts) to work inside of the screen for 30 seconds asynchronous processing.
13 Two point touch is not supported even if matrix touch panel is server.
14 Settings of icons to be displayed on the Display while making a connection from the client can be changed in "SD/USB Removal" in the screen Editor.
("System Settings" - "Display Unit" - "Mode" - "SD/USB Removal") In this setting, a display position and display time can be changed.
15 The "Monopolize touch" function is operated even in Asynchronous Mode. While Screen Change is operated on the client side, touch operation is disabled on the Display side during the predetermined "Monopolize touch".
To prevent this situation from being generated, set "0" (seconds) for "Monopolize touch".
16 [Asynchronous mode]
In asynchronous, when it moves offline mode or transfer mode, data send is canceled and it’s disconnected.
17 When the Display unit and the client are connected, if data send starts, communication between the Display unit and the client is disconnected.
18 In Asynchronous Mode, the same message for one-line error display is displayed on the Display side and the client side.
21 To use Alarm Monitor, the settings also in the GP-Pro EX HMI screen editor are necessary.
20 When using Remote HMI Server, IPC and PC/AT are equivalent to HMI.
21 If you search for a display unit (server) from Pro-face Remote HMI, as its search result, Pro-face Remote HMI displays the IP address of the detected display unit. If the display unit (server) has more than one LAN port, the IP address of one of the multiple Ethernet settings is displayed. As a result, an IP address that is different from the actual IP address Pro-face Remote HMI communicates with may be displayed.
back
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Q&A Index | Product Details (for PC) | Member Registration | Reissue Password | Contact Us
Q&A Index | Product Details (for PC)
Member Registration | Reissue Password | Contact Us
Copyright (C) 2005- Digital Electronics Corporation All Rights Reserved.