What condition shuts down connection between 'Server' and 'Client'?
For connection between 'Server' and 'Client', 'Client' selects a 'Server' and connects/disconnects to/from it basically.

But if the following conditions are satisfied, 'Server' will shut down connection with 'Client'.

1. Timeout
When no operations are performed by 'Client' over a period of time set for timeout in [Pro-face Remote HMI]←[Remote Viewer]←[Display Unit]←[System Settings] of GP-Pro EX Editor

2. At transfer
When a screen is transferred to 'Server' during connection, the 'Server' shuts down connection.

3. Detecting communication shutdown
If there's no shutdown command and no response from 'Client' to 'Server', 'Server' will shut down communication with 'Client' in 30 seconds.

4. Connecting to the second 'Client'
When another 'Client' tries to connect to the 'Server' that has already connected to a 'Client', the 'Server' shuts down connection with the second 'Client'.
* When the number of connected clients is the upper limit, another client is disconnected right after connected.

5. System Variable, #H_RemoteHMI_DisableConnections
When the bit of the system variable, #H_RemoteHMI_DisableConnections is ON, 'Server' shuts down connection with 'Client'.
→"What is the system variable, #H_RemoteHMI_DisableConnections?"
back
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Q&A Index | Product Details (for PC) | Member Registration | Reissue Password | Contact Us
Q&A Index | Product Details (for PC)
Member Registration | Reissue Password | Contact Us
Copyright (C) 2005- Digital Electronics Corporation All Rights Reserved.