T.3.10 After forcing the transfer of the project file, the display unit keeps restarting.

Do you use Siemens AG TIA Portal or Pro-face Remote HMI?

Cause

Display unit's internal memory is insufficient.

Solution

Decrease the size of the transferring project by deleting unnecessary screens, etc.

The guidance of send sizes is as follows.

When using Siemens AG TIA Portal: 10 MB

When using Pro-face Remote HMI: 6 MB