Transfer Status
Select an address to verify the transfer state and result status during the transfer.
Transfer Status Address
Set the address where the transfer status and result are stored.
Error Codes (Results reflected in the error status bits)
0 |
Completed Successfully |
Transfer completed successfully. |
1 |
Reserved |
— |
2 |
No Transfer Condition Number |
For transfer, the Condition Number that corresponds to the specified File Number (GROUP NO) does not exist. |
3 |
Internal Device Range Error |
When transferring from external storage to the device/PLC and the start address is an internal device address, if the transferred data exceeds the internal storage size, this error displays. |
4 |
No external storage |
There is no external storage device inserted into the display unit. CF card cover is open. The USB storage is not formatted properly or is damaged. |
5 |
Read Error |
External storage does not have sufficient free space or was removed in the middle of a write operation. SD card is write protected |
6 |
Write Error |
Reading of data from external storage failed. |
7 |
CF Card Error |
The CF card/SD Card is not formatted properly or is damaged |
8 |
Reserved |
— |
9 |
Reserved |
— |
10 |
Reserved |
— |
11 |
No Condition |
Without the [Enable Data Transmission Feature] settings, a CSV file tries to display on the CSV display from external storage. |
12 |
Write Error |
When transferring data from external storage to the device/PLC, failed to write to the device/PLC. |
13 |
Read Error |
PLC failed to read transferred data on external storage. |
Manual Transfer Timing Chart
Touch the transfer switch and the [Transfer Status Address] Transferring bit (bit 0) turns ON. When a data transfer is completed successfully, the Transferring bit turns OFF and the Transfer Completion bit (bit 1) turns ON. After confirming that the transfer is completed, turn the Transfer Complete Bit OFF.
The Transfer Complete Flag (bit 1) is not turned OFF automatically. Turn it OFF from the device/PLC.