Project data related error
Error Code |
Error Message |
Description |
Solution |
001 |
Area Setting Error |
The area set value is invalid.
|
The project file may not have transferred successfully. Transfer the project file again. |
002 |
Setting value error |
The variable mapped to the terminal is incorrect. Invalid terminal settings. |
|
003 |
Device out-of-range error
|
The variable address allocated to the terminal is not correct.
|
|
004 |
Too many term. setting |
The number of terminals is not correct (too many terminals). |
|
005 |
Terminal setting order error |
The terminal number is not in ascending order. |
|
006 |
Terminal registry short |
The number of terminals is not correct (too few terminals). |
|
007 |
Duplicated Area Settings |
The area is registered twice. |
|
008 |
Too Many Area Settings |
The number of areas is not valid (too many areas). |
|
009 |
Driver settings duplicated |
The driver is registered twice. |
|
010 |
I/O settings inconsistent |
The terminal settings are not correct (Unit I/O settings are not consistent). |
|
011 |
Bit/Integer type inconsistent |
The terminal settings are not correct (Unit variable type settings are not consistent). |
|
012 |
Setting level value error |
The set level (driver/area/terminal) value is invalid. |
|
013 |
Data obtaining address error |
The driver information is not correct. The controller information is not correct. |
|
014 |
Invalid driver ID |
The driver/Module registry results in an error and have not been registered. |
|
015 |
Area Setting Order Error |
The area number is not in ascending order. |
|
016 |
File version mismatch |
Not compatible with the driver's file version |
H/W-related errors
Error Code |
Error Message |
Description |
Solution |
050 |
I/O board ID mismatch |
Wrong board is inserted in the AGP. |
The extended I/F unit may not match or may not be connected. Check the connected extended I/F unit and transfer the project file again. |
051 |
I/O init. error |
Initialization of the IO board has failed. |
The project file may not have been transferred successfully. Transfer the project file again. If the error remains after the transfer, the unit may be broken. Contact the maker of the unit. |
052 |
I/O ROM error |
There is a problem with the system ROM on the I/O board. |
|
053 |
I/O RAM error |
There is a problem with the system RAM on the I/O board. |
|
054 |
I/O IF RAM error |
There is a problem with the system I/F RAM on the I/O board. |
|
055 |
IO EEPROM error |
I/O board EEPROM error |
Application related error
Error Code |
Error Message |
Description |
Solution |
100 |
I/O board response error |
The I/O board does not respond. |
The project file may not have been transferred successfully. Transfer the project file again. If the error remains after transferring, the unit may be broken. Contact the maker of the unit. |
101 |
Short-circuit between D to G |
Short-circuit between D to G |
Check short-circuit between D to G |
102 |
Short-circuit of D-24V |
Short-circuit of D-24V |
Check short-circuit with D-24V. |
103 |
I/O board power error |
The 24V power is not supplied to the I/O board or the voltage is low. |
Check if the 24V power is supplied to the I/O board. |
104 |
Disconnect D or G line |
D-G line is disconnected, the slave unit is broken, or the power is not supplied. |
Check if the D-G line is disconnected or if the slave unit is supplied with power. If the error remains after transferring, the unit may be broken. Contact the maker of the unit. The error code remains until the controller is reset or the system variable #L_IOMasterDrv[0] (Control Address) is cleared. |
105 |
Address recognition data error |
Auto address recognition data is not valid. |
Auto address recognition data may be corrupted. Perform the auto address recognition process again. |
Error codes 101 to 104 may occur at the same time. If errors occur at the same time, errors are shown in the order of priority. The priority order of the error display is 103, 102, 101, 104.
Internal Errors
Error Code |
Error Message |
Description |
Solution |
200 |
Word read error |
Failed to read data from the word type terminal |
The project file may not have been transferred successfully. Transfer the project file again. |
201 |
Bit read error |
Failed to read data from the bit type terminal |
|
202 |
Word write error |
Failed to write data from the word type terminal |
|
203 |
Bit write error |
Failed to write data from the bit type terminal |