Project data error
Logic stop error
Error Code |
Error Message |
Description |
Solution |
---|---|---|---|
001 |
Invalid model |
Unsupported module type |
The project file may not have been sent correctly. Transfer the project file again. |
002 |
Setting value error |
The variable mapped to the terminal is incorrect. Invalid terminal settings. |
|
003 |
Device out-of-range error |
The variable address allocated to the terminal is not correct. |
|
004 |
Too many term. setting |
The number of terminals is not correct (too many terminals). |
|
005 |
Terminal setting order error |
The terminal number is not in ascending order. |
|
006 |
Insufficient number of terminal registration |
The number of terminals is not correct (too few terminals). |
|
007 |
Module settings duplicated |
The module is registered twice. |
|
008 |
Excess module settings |
The number of modules is not correct. (Too many modules) |
|
009 |
Driver settings duplicated |
The driver is registered twice. |
|
010 |
Inconsistent I/O settings |
The terminal settings are not correct (Module I/O settings are not consistent). |
|
011 |
Inconsistent bit/integer type |
The terminal settings are not correct (Module variable type settings are not consistent). |
|
012 |
Setting level value error |
The level of driver is not correct. |
|
013 |
Data obtaining address error |
The driver information is not correct. The controller information is not correct. |
|
014 |
Invalid driver ID |
The driver/Module registry results in an error and have not been registered. |
|
015 |
Module setting order error |
The module number is not in ascending order. |
|
016 |
File version mismatch |
Not compatible with the driver's file version |
H/W-related errors
Logic stop error
Error Code |
Error Message |
Description |
Solution |
050 |
I/O board ID mismatch |
Wrong board is inserted in the AGP or the board is broken |
The display type might not be correct. Check the Display Unit type and transfer the project file again. |
051 |
Unsupported model |
The driver does not support the model. |
|
052 |
I/O board init. error |
The initialization of the IO board fails |
The project file may not have been sent correctly. Transfer the project file again. If this does not resolve the problem, the hardware itself may be broken. Please contact customer support.. |
Application error
I/O update error
Error Code |
Error Message |
Description |
Solution |
100 |
Module init. error |
Either the module is not connected correctly or is broken |
The module may not be properly connected. Reconnect the module properly and turn the power on again. If this does not resolve the problem, the module itself may be broken. Please contact customer support. |
101 |
Module init. resp err |
||
102 |
Module init. send err |
||
103 |
Module init. rcv. err |
||
104 |
Module init. end err |
||
105 |
Module connections err |
Too many connected modules |
The connected I/O board does not match. The display model may be different. Check the display model, and transfer the project file again. |
106 |
Unsupported module |
An unsupported module is connected |
An unsupported module is connected. Remove the unsupported module then turn the power on again. |
107 |
Mode setting error |
Mode setting error |
The project file may not have been sent correctly. Transfer the project file again. |
108 |
Analog data range error |
Problem with the analog module's upper and lower limit values |
|
109 |
Module settings error |
When setup information and connected module do not match |
The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again. |
I/O update continuing error
Error Code |
Error Message |
Description |
Solution |
120 |
Module validation err |
Even when the setup information and module do not match, some operation is available. |
The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again. |
121 |
Module response error |
Either the module is not connected correctly or is broken |
The module may not be properly connected. Reconnect the module properly and turn the power on again. If this does not resolve the problem, the module itself may be broken. Please contact customer support. |
122 |
Module send error |
||
123 |
Module receive error |
||
124 |
Module comm. setting |
Communication data error |
|
125 |
Module ACK error |
Either the module is not connected correctly or is broken |
|
126 |
Module comm. error |
||
127 |
Analog output error |
Writing analog output request flag is incomplete |
The project file may not have been sent correctly. Transfer the project file again. If this does not resolve the problem, the hardware itself may be broken. Please contact customer support. |
128 |
Output data error |
Analog output data range error |
The output data is out of the setting range, or the data output is stopped. Output data within the setting range. |
129 |
Analog power error |
Problem with the analog's external power supply |
An external power supply is not connected to the analog module. Connect a power supply to the analog module. |
130 |
Input data error |
Analog input data range error |
The input data is out of the setting range, or the data input is stopped. Input data within the setting range. |
Internal Errors
I/O update continuing error
Error Code |
Error Message |
Description |
Solution |
200 |
Word read error |
Failed to read data from the word type terminal |
The project file may not have been sent correctly. Transfer the project file again. |
201 |
Bit read error |
Failed to read data from the bit type terminal |
|
202 |
Word write error |
Failed to write data from the word type terminal |
|
203 |
Bit write error |
Failed to write data from the bit type terminal |