19.15.7 XY Historical Scatter Graph - Normalize

To use Auxiliary Lines, [Display Method] must be set to [Display Range].

Normalize

Set to normalize data.

Control Word Address

Set up the address that controls showing and clearing the normalized display.

This can be set to either a PLC address or a display unit's internal device address.

Use a sequence of 3 words from the set address.

Bit 0 and bit 1 of this address control when to show and clear the normalized display.

Store the process status for drawing the normalized graph in this address.

In a normalized display, status bit 0 turns ON while clearing the graph.
In a normalized display, on completion of clearing the graph, status bit 1 turns ON and bit 0 turns OFF.
Confirm status bit 1 is ON, and turn OFF bit 0 of the Control Address.
Turning OFF bit 0 in the Control Address will also turn OFF bit 1 in the status address.
The error status indicates the following error codes.

Error Code

Bit 12 to 15

Description

Details

0

Completed Successfully

Transfer completed successfully.

1

The number of coordinates is 0

When the Number of Coordinates is 0.

2

Display Range Error

Occurs when the following is true: 1) [Display Method] = [Display Range] and display ranges are defined using address values. 2) The difference between the upper and lower limits is 0, or the lower limit is greater than the upper limit.

3

Communication error

A communication (timeout) error occurs when getting coordinates.

4

Reserved

-

 :

 

 

15

Reserved

-

Set the data quantity to store for displaying in a graph. A maximum of 512 coordinates can be set.

X Coordinate Data Start Address

Set the start address of the address area where X coordinate data is stored. The address area used depends on the device designated in [Start Address] and the [Data Type] settings.

Click the icon to display the structure of addresses in use.

For example, when 16 bit device is specified in the address and 16 bit length is set in [Data Type]:

Y Coordinate Data Start Address

Set the start address of the address area where Y coordinate data is stored. The address area used depends on the device designated in [Start Address] and the [Data Type] settings.

Click the icon to display the structure of addresses in use.

For example, when 16 bit device is specified in the address and 16 bit length is set in [Data Type]:

Display

Line Type

Set normalized data as a line.

When selected, select a type of line from among 5 patterns:

  • If the Graph screen is 16 pixels or less, any pattern other than a solid line may not properly display.

Line Thickness

Set the line thickness from 1 to 2.

Display Color

Set the line color.

Background Color

If you selected a line type other than the solid line, set the line's background color.

Pixel Size

Set normalized data as dots.

When selected, select a dot type from among the 7 patterns:,,,,,, . The dot size is fixed at 5 pixels.

Display Color

Set the dot color.

Curve

Specify whether to curve the line within the display range when the data values exceeded the specified value of the display range.

When [Curved Lines] is selected, values that exceed the display range display as the preset upper limit. When both X and Y values exceed the display range, displays the intersecting point between upper limits.

When [Straight Lines] is selected, does not display values that exceed the display range.

  • When displaying a graph, if the 16-bit display range is exceeded, the graph will be curved regardless of the Curve setting.

Connect the start and end points

Specify whether to connect the start and end points of the normalized data to create a closed line.

Blink

Select the blink and blink speed. You can choose different blink settings for [Display Color], [Background Color], and [Graph Area Color].

  • Depending on your display unit's model and [Color] settings, you may not be able to set Blink (from the [Project] menu, point to [System Settings] and click [Display Unit]).
    1.6 Supported Colors