Manual Correction Information

Data for
LT3000 Series Hardware Manual
Errors exist in the manual. Please refer to the following PDF data for correction information.

Type of Error Chapter 2 Specifications, Display Specifications and Input / Output Specifications of DIO Interface (Connector) contains incorrect information such as;

DIO Interface (Connector) Input Specifications, page 2-24

The value of the input ON voltage with 100% of the input derating is "DC24.0 to 26.4V for horizontal mounting, DC24.0 to 25.2V for vertical mounting." The value depends on the mounting directions.


DIO Interface (Connector) Output Specifications, page 2-26 to 2-27

Since the output terminals are not electrically protected, an output line might be short-circuited or a connection fault might burn the external devices and LT. Be sure to install an applicable fuse for each output terminal if there should be the risk for the current running over the rating.

PDF File Please read more details.
LT3300_corrections_eng.pdf (118KB)

Correct Data


If you have problems viewing the PDF file, or require a detailed explanation of the PDF file download procedure, click here.

Last Updated : Dec.19, 2007