| Built-in Interface Specifications
(Type A1/A2) |
 |
 |
I/O Interface Specifications |
 |
 |
Input |
| |
Type A1/A2 |
| Input Voltage |
DC24V |
| Max. Allowable
Voltage |
DC26.4V |
| Input Type |
Sink/Source input |
| Rated Current |
5mA (24V) |
| Input Resistance |
4.7kohm |
| Standard Operating
Range |
ON voltage: 21V min., OFF voltage:
7V max. |
| Input Delay |
OFF
ON: 10ms max., ON
OFF: 10ms max. |
| Common |
1 |
| Common Structure |
16 points/common |
| External Connection |
40-pin connector (also used for
output) |
| Input
Points |
16 |
| Input
Signal Indication |
LED lights for each point ON (logic
side) |
| Isolation
Method |
Photocoupler isolation |
| External
Power Supply |
For Signal: DC24V |
|
Output |
| |
Type A1/A2 |
| Input
Voltage |
DC24V |
| Allowable
Voltage Range |
DC24V±10% |
| Output
Type |
Type A1 |
Sink output |
| Type A2 |
Source output |
| Max.
Load Current |
0.2A/point, 1.6A/common |
| Output
Voltage Drop |
2.5V or less |
| Output
Delay |
OFF
ON: 2ms max., ON
OFF: 2ms max. |
| Leakage
Current when OFF |
0.4mA or less |
| Output
Classification |
Transistor output |
| Common |
1 |
| Common
Structure |
16 points/common |
| External
Connection |
40-pin connector (also used for
input) |
| Output
Protection Classification |
No protection |
| Internal
Fuse |
3.5A chip fuse (not replaceable) |
| Surge
Suppression Circuit |
Diode |
| Output
Points |
16 |
| Output
Signal Indication |
LED lights for each point ON (logic
side) |
| Isolation
Method |
Photocoupler isolation |
| External
Power Supply |
For Signal: DC24V |
|
 |
I/O Interface Connector Specifications, I/O Circuit Diagrams |
 |
 |
The sink/source type DIO integrates 16 input/output points into a compact unit.
The Type A1/A2 LT supports up to 16-point inputs and 16-point outputs, ideal for connecting peripheral I/O devices. |
I/O Connectors (Type A1: Sink Output) |
| Pin |
Signal |
Pin |
Signal |
Front View * |
| A1 |
COM (0V:DOUT) |
B1 |
COM (24V:DIN) |
 |
| A2 |
COM (0V:DOUT) |
B2 |
DC24V (DOUT) |
| A3 |
NC |
B3 |
NC |
| A4 |
NC |
B4 |
NC |
| A5 |
DOUT15 |
B5 |
DIN15 |
| A6 |
DOUT14 |
B6 |
DIN14 |
| A7 |
DOUT13 |
B7 |
DIN13 |
| A8 |
DOUT12 |
B8 |
DIN12 |
| A9 |
DOUT11 |
B9 |
DIN11 |
| A10 |
DOUT10 |
B10 |
DIN10 |
| A11 |
DOUT9 |
B11 |
DIN9 |
| A12 |
DOUT8 |
B12 |
DIN8 |
| A13 |
DOUT7 |
B13 |
DIN7 |
| A14 |
DOUT6 |
B14 |
DIN6 |
| A15 |
DOUT5 |
B15 |
DIN5 |
| A16 |
DOUT4 |
B16 |
DIN4 |
| A17 |
DOUT3 |
B17 |
DIN3 |
| A18 |
DOUT2 |
B18 |
DIN2 |
| A19 |
DOUT1 |
B19 |
DIN1 |
| A20 |
DOUT0 |
B20 |
DIN0 |
* This front diagram shows the connector on the DIO unit side.
When preparing the cable, note that the A and B stamps indicate the number 1 pins. |
|
|
 |
I/O Connectors (Type A2: Source Output) |
| Pin |
Signal |
Pin |
Signal |
Front View * |
| A1 |
COM (24V:DOUT) |
B1 |
COM (0V:DIN) |
 |
| A2 |
COM (24V:DOUT) |
B2 |
0V (DOUT) |
| A3 |
NC |
B3 |
NC |
| A4 |
NC |
B4 |
NC |
| A5 |
DOUT15 |
B5 |
DIN15 |
| A6 |
DOUT14 |
B6 |
DIN14 |
| A7 |
DOUT13 |
B7 |
DIN13 |
| A8 |
DOUT12 |
B8 |
DIN12 |
| A9 |
DOUT11 |
B9 |
DIN11 |
| A10 |
DOUT10 |
B10 |
DIN10 |
| A11 |
DOUT9 |
B11 |
DIN9 |
| A12 |
DOUT8 |
B12 |
DIN8 |
| A13 |
DOUT7 |
B13 |
DIN7 |
| A14 |
DOUT6 |
B14 |
DIN6 |
| A15 |
DOUT5 |
B15 |
DIN5 |
| A16 |
DOUT4 |
B16 |
DIN4 |
| A17 |
DOUT3 |
B17 |
DIN3 |
| A18 |
DOUT2 |
B18 |
DIN2 |
| A19 |
DOUT1 |
B19 |
DIN1 |
| A20 |
DOUT0 |
B20 |
DIN0 |
* This front diagram shows the connector on the DIO unit side.
When preparing the cable, note that the A and B stamps indicate the number 1 pins. |
|
|
 |
Applicable DIO Connector |
| Connection Method |
Applicable Connector |
| Solder-type * |
GLC100-DIOCN01 |
| * A set of FCN-361J040-AU (connector) and FCN-360C040-B (cover) |
|
|
| Manufacturer |
Connection Method |
Applicable Connector |
Fujitsu Takamizawa
Components |
Solder type |
| FCN-361J040-AU |
(Connector) |
| FCN-360C040-B |
(Cover) |
|
| Crimp type |
| FCN-363J040 |
(Connector) |
| FCN-363J-AU/S |
(Contact) |
| FCN-360C040-B |
(Cover) |
|
| Press-fit type |
| FCN-367J040-AU/F |
(Connector) |
|
|
 |
Common I/F Specifications
(Type A1/A2/B+/B/C/H) |
 |
 |
Alarm Output |
| Contact Ratio |
AC125V at 0.15A (resistive load),
DC24V at 0.6A (resistive load) |
| Set Time (at 20°C) |
4ms or less |
| Reset Time (at 20°C) |
4ms or less |
| Min. Switching Load |
1mA/DC5V |
| Initial Contact Resistance |
100mohm or less |
|
|
| When LT Series is powered up and the system is
booted, the relay of the alarm output circuit turns ON. When
a major error or watchdog error occurs, this relay switch turns
OFF. An external fail-safe circuit can be provided to monitor
this relay output. |
 |
Note: This relay switch is OFF from the time the power is turned
on until the LT Series system is booted. The external monitoring
circuit must be started after the LT Series system is booted. |
|
Tool Connector |
| Tool Connector |
Asynchronous: TTL level non-procedural command
Connect data transfer cable for transferring data from LT Editor. |
|
 |
Caution: Before operating any of these products, please be sure to read all related manuals thoroughly. |
|
|
 |
|
 |