Functional Specifications |
 |
 |
|
| Model |
GP2301-SC41-24V |
| Display |
Type |
STN Color LCD |
| Colors |
64 colors |
| Backlight |
CFL (Service life: 50,000hrs,
at 25°C and 24hr. operation) |
| Resolution |
320 x 240 pixels |
| Effective
Display Area (mm) |
115.2(W) x 86.4 (H) |
| Brightness
Control |
4 levels of adjustment available
via touch panel |
| Contrast
Control |
8 levels of adjustment available
via touch panel |
| Language
Character Sets |
ASCII: (Code page 850) Alphanumeric
(incl. European characters)
Chinese: (GB2312-80 codes) simplified Chinese fonts
Japanese: ANK 158, Kanji : 6962 (JIS Standards 1 & 2)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) traditional Chinese fonts |
| Text |
8 x
8 dots |
40 char. x 30 rows |
| 8 x 16 dots |
40 char. x 15 rows |
| 16 x 16 dots |
20 char. x 15 rows |
| 32 x 32 dots*1 |
10 char. x 7 rows |
| Font
Sizes |
Width can be expanded 1 to 8 times.
Height can be expanded 1/2*2, 1 to
8 times. |
| Memory |
Application |
1MB FLASH EPROM - Approx. 320
screens at 3.2KB/screen |
| Data
Backup |
128KB SRAM - uses lithuim battery |
| External
Interfaces |
Serial
Interface (COM1) |
Asynchronous Transmission methods:
RS232C/RS422
Data Length: 7 or 8 bits
Stop Bit: 1 or 2 bits
Parity: None, Odd or Even
Data Transmission Speed: 2400 to 115.2kbps |
| Tool
Connector |
 |
Asynchronous TTL level nonprocedure command
I/F <During Screen File Development>
Used for transferring data between the GP application
software and the GP.
Used for data transfer with the 2-Port feature. <During
Operation>
Used as a bar code reader interface. |
|
| CF
Card Interface |
1 slot (CompactFlashTM) |
*1 Characters twice
the normal size (32 x 32) can be displayed in a high quality
font.
*2 Only available when using the Japanese
character set. |
|
 |
General Specifications |
 |
 |
|
| Model |
GP2301-SC41-24V |
| Electrical |
Rated Voltage |
DC24V |
| Rated Voltage
Range |
DC19.2V to DC28.8V |
| Power Consumption |
22W or less |
| In-Rush Current |
30A or less |
| Allowable Voltage
Drop |
10ms or less
(Actual drop must be less than 1 second) |
| Voltage Endurance |
AC1000V, 20mA for up to 1minute
(between charging and FG terminals) |
| Insulation
Resistance |
20Mohm or more at DC500V
(between charging and FG terminals) |
| Environmental |
Ambient Operating
Temperature |
0°C to +50°C |
| Storage Temperature |
-20°C to +60°C |
| Ambient Humidity |
10%RH to 90% RH (non-condensing) |
| Vibration Resistance |
IEC61131-2 compliant
When vibration is NOT continuous:
10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s2
When vibration is continuous:
10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s2
X,Y,Z dirctions for 10 times (80min.) |
|
Noise Immunity
(via noise simulator) |
Noise Voltage: 1000Vp-p
Pluse Duration: 1 µs
Arise Time: 1ns |
| Dust |
0.1mg/m3 or less (non-conductive
levels) |
| Corrosive
Gasses |
Free of corrosive gasses |
| Structural |
Grounding |
100ohm or less, or your country's
applicable standard*1 |
Ratings
(For front panel of installed unit) |
Equivalent to IP65f (JEM1030)
/ NEMA #250 TYPE 4x/12*2 |
| Weight |
1.2kg (2.6lb) or less |
| Cooling Method |
Natural air circulation |
| External Dimensions |
W171mm[6.73in.] x 138mm[5.43in.]
x D60mm[2.36in.] |
| Panel Cut-out
Dimensions |
156(+1 / -0)mm [6.14in.] x 123.5(+1
/ -0)mm [4.86in.]
(Panel thickness: 1.6mm[0.06in.] to 5mm[0.2in.]) |
| *1 |
Grounding rquirements differ
from country to country. Be sure to confirm your work environment
requirements prior to installation. For more information,
please contact your local Pro-face distributor. |
| *2 |
The degree of protection
provided by these products is equivalent to IP65f, however
their performance cannot be guaranteed for every environment.
Be sure to confirm your work environment requirements prior
to installation. |
|
|
 |
Dimensions (Units:mm [ in.] ) |
 |
 |
|
 |
 |
Caution: Before operating any of these products, please be sure to read all related manuals thoroughly. |
|
|
 |
|
 |