FLEX NETWORK I/O Specifications (16-point Sink Output)

Specifications

Item 16-point Sink Output
Model FN-Y16SK41
E
l
e
c
t
r
i
c
a
l
Unit Rated Voltage DC24V
Allowable Voltage Range DC20.4~28.8V
Allowable Voltage Drop 10ms or less (for DC24V power supply)
Internal Power Consumption Under 1.5W
Voltage Endurance AC1500V at 10mA for 1 minute (between charging and non-charging parts)
Insulation Resistance Above 10Mohm at 500VDC (between charging and non-charging parts)
E
n
v
i
r
o
n
m
e
n
t
a
l
Ambient Operating Temperature 0 ~ 55°C
Storage Temperature -25 ~70°C
Ambient Humidity 30% RH to 95% RH (non-condensing) Level RH-1
Storage Humidity 30% RH to 95% RH (non-condensing) Level RH-1
Dust 0.1mg/m3 or less (non-conductive levels)
Atmosphere Free of corrosive gases
Vibration Resistance 5Hz to 55Hz, 60m/s2 for 2 hours each in X, Y, and Z directions
Noise Immunity (via noise simulator) Noise voltage: 1000Vp-p, Pulse Duration: 1µs, Arise time: 1ns
Electrostatic Discharge Immunity Contact discharge of 6kV (IEC 61000-4-2 Level 3)
S
t
r
u
c
t
u
r
a
l
Mounting Method 35-mm DIN track or screw mounting
Cooling Method Natural air circulation
Weight Max. 0.15kg (0.33lb)
External Dimensions 108mm (W) x 45mm (H) x 49mm (D)
4.25in (W) x 1.77in (H) x 1.92in (D)
Rating IP20
I
n
p
u
t
/
O
u
t
p
u
t
I
n
p
u
t
Input Terminal Rated Voltage -
Input Terminal Allowable
Voltage Range
-
Input Points -
Input Type -
Input ON Voltage -
Input OFF Voltage -
Input Impedance -
Input
Delay
OFF - ON -
ON - OFF -
O
u
t
p
u
t
Output Terminal
Rated Voltage
DC24V
Output Terminal Allowable
Voltage Range
DC20.4~28.8V
Power Consumption -
Output Points 16 points
(open drain sink output)
Output Current 0.2A/point
(16 points/1 common, max. common current 2.0A)
Max. Load Current -
Short-circuit Protection None
Voltage Drop (ON Voltage) Max. DC1.5V
Clamp Voltage DC39V±1V
Leakage Current 0.1mA
Output
Delay
OFF - ON Max. 1ms
ON - OFF Max. 1ms
Contact Rating -
Min. Closing Load -
Initial Contact Resistance -
Electrical Lifetime -
Mechanical Lifetime -
Occupied Node Number 1

FLEX NETWORK I/O Circuit Diagrams