| FGW-SE41-24V |
| Electrical |
Rated
Voltage
(Rated Voltage Range) |
DC24V (DC19.2V to DC28.8V) |
Allowable
Voltage
Interruption |
10ms or less |
| Power Consumption |
10W or less |
| In-rush Current |
30A or less |
| Voltage Endurance |
AC 500V, 20mA for up to 1 minute
(between charging and FG terminals) |
| Insulation Resistance |
10Mohm or more at DC500V (between
charging and FG terminals) |
| Environment |
Operating
Temperature/Storage
Temperature |
0°C to 55°C / -20°C
to +60°C |
| Humidity / Storage
Humidity |
10%RH to 90%RH (non-condensing,
wet bulb temperature: 39°C or less) |
| Air Purity (Dust) |
0.1 mg/m3 or less (non-conductive
levels) |
| Corrosive Gasses |
Free of corrosive gasses |
Atmospheric
Pressure |
800 hpa to 1114 hpa (2000 meters
or lower) |
| Vibration Endurance |
IEC61131-2(JIS B 3501)Compliant
When vibration is NOT continuous:10Hz to 57Hz 0.075mm, 57Hz
to 150Hz 9.8m/s
When vibration is continuous:10Hz to 57Hz 0.035mm, 57Hz to 150Hz
4.9m/s
X, Y, Z directions for 10 times (80min.) |
| Shock Resistance |
IEC61131-2 (JIS B 3501) Compliant
147m/s, X, Y, Z directions for 3 times |
Noise Immunity
(via noise simulator) |
Noise Voltage: 1200Vp-p
Pulse Duration: 1µs
Rise Time: 1ns |
| Structual |
Electrostatic
Discharge
Immunity |
6kV (IEC 61000-4-2 Level 3) |
| Grounding |
100 ohm or less, or your country's
applicable standard* |
| Cooling Method |
Natural air circulation |
| Installation |
DIN rail mount |
| Certifications |
EN55011 class A, EN61000-6-2,
UL508, CAN/CSA-C22.2 No.1010 |
| Weight |
0.6kg [1.3lb.] or less (main unit
only) |
| External Dimensions |
W37[1.46] x H131[5.16] x D105[4.13]
mm[in.] (excluding projections) |