 RHAA070(Node Name): The cable has been disconnected or the target has been powered off

Error Details

The error message [RHAA070(Node Name): The cable has been disconnected or the target has been powered off] appeared on the GP3000 screen.

Causes

1. The display model set in GP-Pro EX is not matched to your GP model in use.
2. The power of the device/PLC is OFF.
3. The cable wiring is wrong, or the cable is not correctly connected.
4. In [Device/PLC Settings], the correct [SIO Type] is not selected

Actions

1. Check the model of your display in GP-Pro EX.
Display Settings
2. Check if the power of the device/PLC is ON.
3. Refer to the corresponding Device/PLC Connection Manual and check if the cable wiring is right and if the cable is correctly connected.
4. Check if the [SIO Type] is correct in [Device/PLC Settings].
Communication Settings in GP-Pro EX