RHAA050(Node Name): Unknown devices exist in write devices

Error Details

The error message [RHAA050(Node Name): Unknown devices exist in write devices] appeared on the GP3000 screen.

Causes

This error occurs if the write address is out of the device address range when using the offset value address or indirect specification feature in a Data Display or another part.

Actions

1. Check the addresses used on the screen on which the error occurred.
If you set the offset value address or indirect specification feature, make sure that it is within the address range.
2. If the error occurred in all screens, check the addresses of the functions that operate in all screens, such as Alarm, Sampling and Global D-script.
If you set the offset value address or indirect specification feature, make sure that it is within the address range.

What is the Global D-script?
The Global D-script is one of the programming functions that a touch panel has. With this function, all screens in the project file can be programmed by one D-script.