 Wish to display the designated window on the selected place.
 
By using Window Parts, you cannot move the place of window. However, by using [Indirect] of U-tag, you can display the designated window on the selected place.
    
 
- U-tag Indirect
  1.In the U-tag Setting dialog box, select [Indirect] in [Designated Window].
 
   
 

2.Input the Word Address.

 
  The 4 consecutive Word Addresses are used for U-tag, beginning from this word address.
As for the example above, 4 consecutive Word Addresses beginning from D100 are used.
(D100, 101, 102, 103)
   
  3. Write the required data to the Word Address designated in procedure 2.
 
 
Roles
Details
Address+0
Window Control
ON: Display the window
OFF: Hide the window
Address+1
Window Registration No.
Store the number registered on Window Registration.
If you wish to switch the window to be displayed, please change the value of this address.
Address+2
Window Display Coordinates (X-axis)
Store the coordinate position to display.
If you wish to change the position of window display, please change the value of this address.

Address+3

Window Display Coordinates (Y-axis)
   
 