Products
Download
Contact us
Back to Top
 FAQ
Alarm message is not displayed on Q-tag
 
Please check the following points.
 

Is the Bit Address registered in the Alarm Editor ON?

   
Have you registered the alarm message on [Bit Log Alarm] or [Word Log Alarm] of [Alarm Editor]?
 
   
   
[Have you set the [State] of [Alarm Editor] ON or OFF?
[If you set [On], alarm occurs when the bit is ON. On the other hand, if you set [Off], alarm occurs when the Bit is OFF.
 
 
Is the setting of [Display Start Line]'s value appropriate? (Check from [Q Tag Settings] dialog box→ [.Display Mode]→ [Display Start Line]). At first, set [1] and check the operation.
 

Is the [Size/Color] settings right? Aren't the FG color and the BG color set to be the same?

 
 
Is the PLC address registered in [Alarm Editor] right? Please place a lamp on the Base screen and check whether the bit turns ON/OFF.
In [Extended Settings] of [GP System Settings], click on [Q Tag Settings] and check if the number of [Q Tag Setting] is not set to zero.
   
       
Execute [Rebuilt] and select [Force System Setup] in [Transfer Settings]. Then, transfer the screen data to GP unit again.
 
 
 
Return to Top Back
FAQ for use | Protection of Personal Information | Trademark Acknowledgments | About Intellectual Property Rights | Terms of Use
Copyright (C) 2005- Schneider Electric Japan Holdings Ltd. All Rights Reserved.