Features available in GP-Viewer EX are different than those used with the display unit.
Feature
|
Details
|
Switch
|
-
AUX Output cannot be used.
-
Special switches related to security, resetting, offline or other unsupported features cannot be used.
-
If switches overlap, or multiple switch functions are set up, operations may differ from the display unit.
|
Sampling Display
|
-
You cannot edit data.
-
First gets all sampling information, and then updates at the frequency specified in GP-Viewer EX. From the [Tool] menu click [Settings] and note the [Update Cycle] field.
-
Refine Search/Sort is available, but it does not synchronize with the display unit.
|
Alarm feature
|
-
The Sub Display feature may be executed at an unexpected time by operation on the display unit even when the Alarm part is not displayed.
-
Alarm information cannot be cleared by external operation.
-
Display content may be displayed differently than the display unit (time information, active alarm status, and so on). Touching the [Screen Update] button will update the contents by re-acquiring the alarm information.
-
You cannot save alarm information.
-
You cannot perform [Acknowledged] or [Clear] operation.
-
You cannot perform [Alarm Number Acquisition] operation.
-
If alarm analysis is used, the analysis list is not shown on the operation log.
-
Refine Search/Sort is available, but it does not synchronize with the display unit.
|
Logic Programing
Global D-Script
Extended Script
|
|
D-script
|
|
Trigger Action
|
-
This feature is executed in Asynchronous Mode when the same screen is displayed. In this case, changing screens on the display unit does not change screens in GP-Viewer EX. Therefore, execution of [Start Application] or [Exit WinGP] cannot be confirmed by GP-Viewer EX, so do not perform such operations from GP-Viewer EX.
-
This feature is enabled in Synchronous Mode. However, the results of drawing are not reflected.
|
Screen Capture
|
|
Error
|
-
Displays errors on both the display unit and GP-Viewer EX.
-
All errors are acquired at first and then the information is updated at the frequency specified in GP-Viewer EX. Click [Change setting] and select [Information of Automatic update frequency].
-
Errors that are restored will not disappear. Such errors disappear only when the screen is changed.
|
Data Display
|
|
Historical Trend Graph
|
|
Data Block Display Graph
|
|
XY Historical Scatter Graph
|
|
XY Block Display Scatter Graph
XY Historical Scatter Graph Normalization
|
-
When quickly changing the control word using D-Script or a PLC with ladder logic on the display unit, server operations may not be detected.
-
In Asynchronous Mode, when updating the graph, its Display Completion bit does not turn ON. Therefore, the control word cannot be returned to 0 on the display unit. Prior to updating, create a switch that returns the control word to 0.
|
Bulletin Message
|
-
When you perform a display/hide operation continuously, display contents may not be synchronized with the display unit.
-
In order to update the message, clear the message and display it again.
-
Display Completion bit cannot be used.
|
Recipes
|
|
Enhanced Recipes
|
|
File Manager
|
|
Internal Devices (LS Area, Memory Link)
|
-
You cannot write data in the Special Relay Area (LS2071 to LS2074, LS2078 to LS2095) from the Viewer.
-
Write operation into Special Relay Area and Extend System Area is not supported.
|
Security feature
|
-
To change or clear the security level, from the Menu, point to Feature, and select "Change Security Level" or "Change User ID".
You can set the security level to 0 if you leave the user ID/password field blank and press the OK button. (This cannot be completed when the security is set for reading Viewer data.)
|
Operation Log
|
|
Web Server and FTP Features
|
|
RPA Function
|
|
Printing feature
|
|
Transfer Project File
|
|
Monitor
|
|
2-color Backlight Switching
|
|
Function Key
|
|
Playing Movies
|
-
You cannot record or play movies.
-
Movie Players and Image Unit Displays will not display.
-
Image Sensor Displays will not show video images.
|
Japanese FEP (Help)
|
|
Others
|
-
The status address of each part/function, search status address, and cursor information storage address information cannot be obtained.
-
Even if [Reverse Display] is enabled in System Settings [Display Unit]-[Display Settings], reverse display is not possible.
-
The screen does not change to the standby mode.
The display unit will switch to standby mode, but the screen will not be changed while the Viewer is connected.
-
You cannot adjust the brightness and contrast.
-
Cannot change to offline mode.
-
A bar code reader cannot be connected.
-
Cannot be connected to a modem.
-
You cannot check tag consistency.
-
Does not respond to the station search of Pro-Server EX.
-
The time displayed on GP-Viewer EX is based on the time settings of your computer.
|