During the global interlock, Touch Operations on the screen are disabled. However, it is possible to perform Touch Operations for the following features, in the same way as normal.
Displaying and operating the System Menu
Displaying and operating the Brightness/Contrast adjustment bar
Changing the Error Window (single-line = details) and deleting it
Returning from standby mode (Screen OFF)
Offline Mode Operations
If the features or parts are touched when touching them has been disabled by the global interlock, the touch buzzer sound does not sound, and AUX is not output.
During the global interlock, do not activate the Ladder Monitor, the Device Monitor, the Logic Monitor, or the Address Monitor. If you activate them, you cannot exit any monitor feature because touch operation is disabled.