One Sampling Data Display can be placed per screen. If multiple Displays are on one screen, only the Display set first is active.
The data edit function is disabled when the Sampling Data Display is placed on a Window screen.
A Sampling Data Display cannot be set to the same screen as a Special Data Display [Show CSV] or a Data Display which uses a pop-up keypad.
The calculation operations are carried out in 32 bit length. If the calculation data has more digits (exceeds 32 bits), the calculation will not display correctly.
When the [Overwrite old data after finishing the specified cycles] check box is selected, the calculation rows (Total, Average, Max, Min) will show the calculated value of the data housed in the display unit. Overwritten data is not included in the calculations.
When the [Overwrite old data after finishing the specified cycles] is selected in the [Mode] tab, and in the [Display/Save in CSV] tab you click [Data Type] and select [Specify Input/Display Range] to define the [Min]/[Max] values, the sampling display update will be slower as the number of sampling cycles increases.
Calculations use values after rounding off. When alarms are set up in the data portion, the alarm range is determined by the value before rounding off. As a result, even if the data and calculation have the same alarm range, the display color may be different.
In the sampling group's Address, if the [Bit Length] or [Addressing] change, the [Display/Save in CSV] format will be reset.
When changing the [Display/Save in CSV] settings from [Custom Settings] to [Basic], all customized settings will be reset.
Please use the same data format for the numeric value and total fields. If the formats differ, then the calculated value may not display correctly.
When [Always] is selected for [Condition for Read Alarm Value], the number of indirect addresses for alerts is up to 512. The upper and lower limits are a sequence of two words and one device. An indirect address exceeding 512 data items is invalid, and an alarm will not be operated.
In regards to Calculation Settings, when [Calculated Data] is [Total] or [Average], the average or total values are not calculated from the Sampled Data, but rather from the Calculation Settings results. As a result, a deviation may result between the data and calculated values.