The DIO output module defines fallback mode and values using configuration objects.
Object (Hex) |
Sub index |
Bit |
Parameter |
6200 |
n |
(0) Output 0 ... (7) Output 7 |
8 bit word |
6300 |
n |
(0) Output 0 ... (7) Output 7 |
16 bit word |
(8 to 15) Unused |
|||
6302 |
n |
(0) Polarity output 0 ... (7) Polarity output 7 |
0: Normally open output (NO) (initial value) 1: Normally closed output (NC) |
(8 to 15) Unused |
|||
6306 |
n |
(0) Fallback mode output 0 ... (7) Fallback mode output 7 |
0: Retentive State 1: Fallback value enabled (initial value) (set to the set fallback value) |
(8 to 15) Unused |
|||
6307 |
n |
(0) Fallback value output 0 ... (7) Fallback value output 7 |
0: Fallback to 0 (initial value) 1: Fallback to 1 |
(8 to 15) Unused |
|||
6308 |
n |
(0) Output mask 0 ... (7) Output mask 7 |
0: Retentive State (initial value) 1: Value of the object (Hex) 6300 |
(8 to 15) Unused |