30.7.6.4 Standard Output (Model: EXM-DDO8UT, EXM-DDO8TT and EXM-DRA8RT)

The DIO output module defines fallback mode and values using configuration objects.

Object (Hex)

Sub index

Bit

Parameter

6200

n

(0) Output 0

...

(7) Output 7

8 bit word

6300

n

(0) Output 0

...

(7) Output 7

16 bit word

(8 to 15) Unused

6302

n

(0) Polarity output 0

...

(7) Polarity output 7

0: Normally open output (NO) (initial value)

1: Normally closed output (NC)

(8 to 15) Unused

6306

n

(0) Fallback mode output 0

...

(7) Fallback mode output 7

0: Retentive State

1: Fallback value enabled (initial value) (set to the set fallback value)

(8 to 15) Unused

6307

n

(0) Fallback value output 0

...

(7) Fallback value output 7

0: Fallback to 0 (initial value)

1: Fallback to 1

(8 to 15) Unused

6308

n

(0) Output mask 0

...

(7) Output mask 7

0: Retentive State (initial value)

1: Value of the object (Hex) 6300

(8 to 15) Unused