This object indicates time interval between two SYNC signals. This interval is at least 10ms and the minimum increment needs to be 1ms. It must be entered with double word.
Field is set to 0 when this object is not used.
When the value 10,000 to 10,000,000 is entered, HTB needs to receive SYNC signals within this time interval. If it is not received, it is shifted to pre-operational state. Maximum tolerance is 1% of the set value. Monitoring elapsed time starts when the first SYNC signal is received.
If the setting is other than 0, set a larger global SYNC period than the master side's global SYNC period When a global SYNC period smaller than the global SYNC period of the master side is set, an error message will be displayed.
Properties of the object
Object properties:
Sub index |
Description |
Data Type Default |
Access PDO mapping Backup |
0 |
- |
UNSIGNED32 0 |
rw (read-write) × ○ |
Coding switching cycle period
Threshold is shown in the following table.
Value type |
Decimal value |
Hexadecimal value |
Synchronization interval (ms) |
Standard value |
0 |
0000 0000 |
- |
Min |
10000 |
0000 2710 |
10 |
- |
25000 |
0000 61A8 |
25 |
- |
250000 |
0003 D090 |
250 |
- |
1000000 |
000F 4240 |
1000 |
- |
5000000 |
004C 4B40 |
5000 |
Max |
10000000 |
0098 9680 |
10000 |