30.7.10.6 Object 1006h: Global SYNC period

This object indicates time interval between two SYNC signals. This interval is at least 10ms and the minimum increment needs to be 1ms. It must be entered with double word.

Field is set to 0 when this object is not used.

When the value 10,000 to 10,000,000 is entered, HTB needs to receive SYNC signals within this time interval. If it is not received, it is shifted to pre-operational state. Maximum tolerance is 1% of the set value. Monitoring elapsed time starts when the first SYNC signal is received.

Properties of the object

Object properties:

Sub index

Description

Data Type

Default

Access

PDO mapping

Backup

0

-

UNSIGNED32

0

rw (read-write)

×

 

Coding switching cycle period

Threshold is shown in the following table.

Value type

Decimal value

Hexadecimal value

Synchronization interval (ms)

Standard value

0

0000 0000

-

Min

10000

0000 2710

10

-

25000

0000 61A8

25

-

250000

0003 D090

250

-

1000000

000F 4240

1000

-

5000000

004C 4B40

5000

Max

10000000

0098 9680

10000