Project data error
Logic stop error
Error Code |
Error Message |
Description |
Solution |
---|---|---|---|
001 |
Module type error |
Unsupported module type |
The project file might not have been sent properly. Transfer the project file again. |
002 |
Setting value error |
The variable mapped to the terminal is incorrect. Invalid terminal settings |
|
003 |
Device out-of-range error |
The variable address allocated to the terminal is not correct. |
|
004 |
Excess terminal settings |
The number of terminals is not correct. (Too many terminals) |
|
005 |
Terminal setting order error |
The terminal no. is not in ascending order. |
|
006 |
Terminal registry short |
The number of terminals is not correct. (Too few terminals) |
|
007 |
Module settings duplicated |
The module is registered twice. |
|
008 |
Excess module settings |
The number of modules is not correct. (Too many modules) |
|
009 |
Driver settings duplicated |
The driver is registered twice. |
|
010 |
I/O settings inconsistent |
The terminal settings are not correct (Module I/O settings are not consistent). |
|
011 |
Bit/Integer type inconsistent |
The terminal settings are not correct (Module variable type settings are not consistent). |
|
012 |
Setting level value error |
The driver is not correct. |
|
013 |
Data obtaining address error |
The driver information is in correct. The controller information is not correct. |
|
014 |
Driver ID error |
The driver/Module registry results in an error and have not been registered. |
|
015 |
Module setting order error |
The module number is not in ascending order. |
|
016 |
File Version Error |
Not compatible with the driver's file version |
H/W related error
Logic stop error
Error Code |
Error Message |
Description |
Solution |
050 |
I/O board ID different |
The connected I/O board is not correct. |
The display type might not be correct. Check the display type and transfer the project file again. |
051 |
Unsupported model error |
The driver does not support the model. |
|
052 |
I/O board initialization error |
The I/O board initialization fails. |
The project file might not have been sent properly. Transfer the project file again. If the problem is still not solved, there may be a problem with the hardware. Contact your support center. |
Application error
I/O update error
Error Code |
Error Message |
Description |
Solution |
100 |
Module initialization error |
Either the module is not connected correctly or is broken |
Critical Failure Module may not be connected correctly. Reconnect the module and turn the power on again. If this does not resolve the problem, the module itself may be broken. Contact your support center. |
101 |
Module initialization response error |
||
102 |
Module initialize send error |
||
103 |
Module initialize receive error |
||
104 |
Module initialization end error |
||
105 |
Module connection count error |
Too many connected modules |
There are too many modules connected. Reduce the number of modules to an acceptable number then turn the power on again. |
106 |
Unsupported module |
An unsupported module is connected |
An unsupported module is connected. Remove the unsupported module then turn the power on again. |
107 |
Mode setup value error |
Mode setup value error |
The project file might not have been sent properly. Transfer the project file again. |
108 |
Analog data range error |
Analog module maximum/minimum value setup error |
|
109 |
Module setup error |
When setup information and connected module do not match |
The setup information in the project and the connected module are different. Connect the defined module and turn the power back on. |
I/O update continuing error
Error Code |
Error Message |
Description |
Solution |
120 |
Module verification error |
When the setup information and module do not match |
The setup information in the project and the connected module are different. Connect the defined module and turn the power back on. |
121 |
Module response error |
Either the module is not connected correctly or is broken |
Critical Failure Module may not be connected correctly. Reconnect the module and turn the power on again. If this does not resolve the problem, the module itself may be broken. Contact your support center. |
122 |
Module send error |
||
123 |
Module receive error |
||
124 |
Module communication setup error |
Communication data error |
|
125 |
Module ACK error |
Either the module is not connected correctly or is broken |
|
126 |
Module communication error |
||
127 |
Analog output error |
Writing analog output request flag is incomplete |
The project file might not have been sent properly. Transfer the project file again. If the problem is still not solved, there may be a problem with the hardware. Contact your support center. |
128 |
Output data error |
Analog output data range error |
Output data is outside the setup range or output is stopped. Output data in the defined range. |
129 |
Analog external power error |
Problem with the analog's external power supply |
An external power supply is not powering the analog module. Connect power to the analog module. |
130 |
Input data error |
Analog input data range error |
Input data is outside the setup range or input is stopped. Input data in the defined range. |
Internal error
I/O update continuing error
Error Code |
Error Message |
Description |
Solution |
200 |
Integer type data read error. |
Reading the integer type terminal data value failed. |
The project file might not have been sent properly. Transfer the project file again. |
201 |
Bit type data read error |
Reading the bit type terminal data value failed. |
|
202 |
Integer type data write error |
Writing the integer type terminal data value failed. |
|
203 |
Bit type data write error |
Writing the bit type terminal data value failed. |