30.6.3.1 Error Code - LT and EX Module

Project data error

Logic stop error

Error Code

Error Message

Description

Solution

001

Module type error

Unsupported module type

The project file might not have been sent properly.

Transfer the project file again.

002

Setting value error

The variable mapped to the terminal is incorrect.

Invalid terminal settings

003

Device out-of-range error

The variable address allocated to the terminal is not correct.

004

Excess terminal settings

The number of terminals is not correct. (Too many terminals)

005

Terminal setting order error

The terminal no. is not in ascending order.

006

Terminal registry short

The number of terminals is not correct. (Too few terminals)

007

Module settings duplicated

The module is registered twice.

008

Excess module settings

The number of modules is not correct. (Too many modules)

009

Driver settings duplicated

The driver is registered twice.

010

I/O settings inconsistent

The terminal settings are not correct (Module I/O settings are not consistent).

011

Bit/Integer type inconsistent

The terminal settings are not correct (Module variable type settings are not consistent).

012

Setting level value error

The driver is not correct.

013

Data obtaining address error

The driver information is in correct.

The controller information is not correct.

014

Driver ID error

The driver/Module registry results in an error and have not been registered.

015

Module setting order error

The module number is not in ascending order.

016

File Version Error

Not compatible with the driver's file version

 

H/W related error

Logic stop error

Error Code

Error Message

Description

Solution

050

I/O board ID different

The connected I/O board is not correct.

The display type might not be correct.

Check the display type and transfer the project file again.

051

Unsupported model error

The driver does not support the model.

052

I/O board initialization error

The I/O board initialization fails.

The project file might not have been sent properly.

Transfer the project file again.

If the problem is still not solved, there may be a problem with the hardware. Contact your support center.

 

Application error

I/O update error

Error Code

Error Message

Description

Solution

100

Module initialization error

Either the module is not connected correctly or is broken

Critical Failure Module may not be connected correctly. Reconnect the module and turn the power on again.

If this does not resolve the problem, the module itself may be broken. Contact your support center.

101

Module initialization response error

102

Module initialize send error

103

Module initialize receive error

104

Module initialization end error

105

Module connection count error

Too many connected modules

There are too many modules connected. Reduce the number of modules to an acceptable number then turn the power on again.

106

Unsupported module

An unsupported module is connected

An unsupported module is connected. Remove the unsupported module then turn the power on again.

107

Mode setup value error

Mode setup value error

The project file might not have been sent properly. Transfer the project file again.

108

Analog data range error

Analog module maximum/minimum value setup error

109

Module setup error

When setup information and connected module do not match

The setup information in the project and the connected module are different. Connect the defined module and turn the power back on.

I/O update continuing error

Error Code

Error Message

Description

Solution

120

Module verification error

When the setup information and module do not match

The setup information in the project and the connected module are different. Connect the defined module and turn the power back on.

121

Module response error

Either the module is not connected correctly or is broken

Critical Failure Module may not be connected correctly. Reconnect the module and turn the power on again.

If this does not resolve the problem, the module itself may be broken. Contact your support center.

122

Module send error

123

Module receive error

124

Module communication setup error

Communication data error

125

Module ACK error

Either the module is not connected correctly or is broken

126

Module communication error

127

Analog output error

Writing analog output request flag is incomplete

The project file might not have been sent properly. Transfer the project file again.

If the problem is still not solved, there may be a problem with the hardware. Contact your support center.

128

Output data error

Analog output data range error

Output data is outside the setup range or output is stopped. Output data in the defined range.

129

Analog external power error

Problem with the analog's external power supply

An external power supply is not powering the analog module. Connect power to the analog module.

130

Input data error

Analog input data range error

Input data is outside the setup range or input is stopped. Input data in the defined range.

 

Internal error

I/O update continuing error

Error Code

Error Message

Description

Solution

200

Integer type data read error.

Reading the integer type terminal data value failed.

The project file might not have been sent properly.

Transfer the project file again.

201

Bit type data read error

Reading the bit type terminal data value failed.

202

Integer type data write error

Writing the integer type terminal data value failed.

203

Bit type data write error

Writing the bit type terminal data value failed.