Restore last saved parameters.
When parameters are restored in "action" state, unexpected actions may occur in the equipment resulting in damage and physical injury. If it is necessary to operate, set HTB in the "pre-action" state, or ensure physical and equipment safety before attempting other operations.
Failure to follow these instructions may result in serious injury or death.
To restore parameters, you need to write the text string "load" to the corresponding index. You may need to reverse the string to "daol" or 64616F6Ch.
When the restoration proceeds (object 3202h is state 0), this command is ignored.
Parameters are restored immediately.
Properties
Object properties:
Sub index |
Description |
Data Type Default |
Access PDO mapping Backup |
0 |
Restore specific application parameters |
UNSIGNED32 1 |
rw (read-write) × × |
Restored objects are as follows.
1005h, 1006h, 100Ch, 100Dh, 1014h, 1016h, 1017h, 1400h to 1407h, 1600h to 1607h, 1800h to 1807h, 1A00h o 1A07h,
2000h, 2100h, 2101h, 2102h, 2103h, 2104h, 2105h, 2106h, 2200h, 2201h, 2202h, 2203h, 2303h, 2304h, 2305h, 2306h, 2307h, 2354h, 2355h, 2403h, 2404h, 2405h, 2406h, 2407h, 2408h, 2409h, 240Ah, 2454h, 2455h, 2457h, 2458h, 2502h, 2503h, 2504h, 2505h, 2506h, 2507h, 2508h, 2557h,
6102h, 6103h, 6302h, 6306h, 6307h, 6308h, 6421h, 6424h, 6425h, 6443h, 6444h