Power for the analog module should be separate from the display unit's power supply and it should be turned on at least 1 second ahead. When turning the LT unit ON, first supply the module with power for 1 second or longer before you turn ON the LT unit. The display unit may not operate correctly if it is restarted too quickly.
When using the analog module (set up with 4 to 20 mA), and signals are less than 4 mA or greater than 20 mA, an abnormal data error message displays. In this scenario, inputs retain their previous values before the error.
Internal communication between the display unit and TM3 module may experience a maximum delay of scan time + 20 milliseconds.
In addition, because the TM3 module (hardware) also has a delay, to calculate the actual delay time for inputs and outputs, also add the TM3 module delay time.
The number of TM3 modules that can be connected
The number of TM3 modules that can be connected differs depending on the display unit or TM3 module type used. Please refer to the following table for details.
Series |
Number of units |
TM3 Modules that can be connected |
STC6000 Series*1 |
1 |
All TM3 Modules |
2 |
TM3 module in group A, B and C, as below |
*1 To connect three EX modules to STC6000 Series, the relay unit (TM3XTRA1/TM3XREC1) is required.
TM3 Modules in Each Group
Groups |
TM3 Module Name |
A |
TM3DI16K TM3DQ16U TM3DQ16UK TM3DQ16TK |
B |
TM3DI8 TM3DI8A TM3DI16 TM3DQ8R TM3DQ16R TM3DQ8U TM3DQ8T TM3DQ16T TM3DM8R TM3AI2H TM3AI4 TM3AI8 TM3TI4 TM3TI4D TM3AQ2 TM3AQ4 TM3TM3 TM3AM6 TM3XTRA1 |
C |
TM3DI32K TM3DQ32UK TM3DQ32TK |
D |
TM3DM24R |
When changing from the STC6000 series to other models
All TM3 driver and TM3 module settings will be deleted.