31.6.3.1 Error Code - LT3000 / STC6000 Series and EX Module

Project data error

Logic stop error

Error Code

Error Message

Description

Solution

001

Invalid model

Unsupported module type

The project file may not have been sent correctly.

Transfer the project file again.

002

Setting value error

The variable mapped to the terminal is incorrect.

Invalid terminal settings.

003

Device out-of-range error

The variable address allocated to the terminal is not correct.

004

Too many term. setting

The number of terminals is not correct (too many terminals).

005

Terminal setting order error

The terminal number is not in ascending order.

006

Insufficient number of terminal registration

The number of terminals is not correct (too few terminals).

007

Module settings duplicated

The module is registered twice.

008

Excess module settings

The number of modules is not correct. (Too many modules)

009

Driver settings duplicated

The driver is registered twice.

010

Inconsistent I/O settings

The terminal settings are not correct (Module I/O settings are not consistent).

011

Inconsistent bit/integer type

The terminal settings are not correct (Module variable type settings are not consistent).

012

Setting level value error

The level of driver is not correct.

013

Data obtaining address error

The driver information is not correct.

The controller information is not correct.

014

Invalid driver ID

The driver/Module registry results in an error and have not been registered.

015

Module setting order error

The module number is not in ascending order.

016

File version mismatch

Not compatible with the driver's file version

 

H/W-related errors

Logic stop error

Error Code

Error Message

Description

Solution

050

I/O board ID mismatch

Wrong board is inserted in the AGP or the board is broken

The display type might not be correct.

Check the Display Unit type and transfer the project file again.

051

Unsupported model

The driver does not support the model.

052

I/O board init. error

The initialization of the IO board fails

The project file may not have been sent correctly.

Transfer the project file again.

If this does not resolve the problem, the hardware itself may be broken. Please contact customer support..

 

Application error

I/O update error

Error Code

Error Message

Description

Solution

100

Module init. error

Either the module is not connected correctly or is broken

The module may not be properly connected. Reconnect the module properly and turn the power on again.

If this does not resolve the problem, the module itself may be broken. Please contact customer support.

101

Module init. resp err

102

Module init. send err

103

Module init. rcv. err

104

Module init. end err

105

Module connections err

Too many connected modules

The connected I/O board does not match. The display model may be different. Check the display model, and transfer the project file again.

106

Unsupported module

An unsupported module is connected

An unsupported module is connected. Remove the unsupported module then turn the power on again.

107

Mode setting error

Mode setting error

The project file may not have been sent correctly. Transfer the project file again.

108

Analog data range error

Problem with the analog module's upper and lower limit values

109

Module settings error

When setup information and connected module do not match

The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again.

I/O update continuing error

Error Code

Error Message

Description

Solution

120

Module validation err

Even when the setup information and module do not match, some operation is available.

The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again.

121

Module response error

Either the module is not connected correctly or is broken

The module may not be properly connected. Reconnect the module properly and turn the power on again.

If this does not resolve the problem, the module itself may be broken. Please contact customer support.

122

Module send error

123

Module receive error

124

Module comm. setting

Communication data error

125

Module ACK error

Either the module is not connected correctly or is broken

126

Module comm. error

127

Analog output error

Writing analog output request flag is incomplete

The project file may not have been sent correctly. Transfer the project file again.

If this does not resolve the problem, the hardware itself may be broken. Please contact customer support.

128

Output data error

Analog output data range error

The output data is out of the setting range, or the data output is stopped. Output data within the setting range.

129

Analog power error

Problem with the analog's external power supply

An external power supply is not connected to the analog module. Connect a power supply to the analog module.

130

Input data error

Analog input data range error

The input data is out of the setting range, or the data input is stopped. Input data within the setting range.

 

Internal Errors

I/O update continuing error

Error Code

Error Message

Description

Solution

200

Word read error

Failed to read data from the word type terminal

The project file may not have been sent correctly.

Transfer the project file again.

201

Bit read error

Failed to read data from the bit type terminal

202

Word write error

Failed to write data from the word type terminal

203

Bit write error

Failed to write data from the bit type terminal